![ABB i-bus KNX Room Master Premium RM/S 2.1 Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/abb/i-bus-knx-room-master-premium-rm-s-2-1/i-bus-knx-room-master-premium-rm-s-2-1_product-manual_3076019.webp)
ABB i-bus
®
KNX
Device technology
© 2008 ABB STOTZ-KONTAKT GmbH
17
2.1.5
Lamp load output
Lamps
Incandescent lamp load
2300 W
Fluorescent lamp T5 / T8
Uncorrected
Parallel compensated
DUO circuit
2300 W
1500 W
1500 W
Low-voltage halogen lamps
Inductive transformer
Electronic transformer
1200 W
1500 W
Halogen lamp 230 V
2300 W
Dulux lamp
Uncorrected
Parallel compensated
1100 W
1100 W
Mercury-vapour lamp
Uncorrected
Parallel compensated
2000 W
2000 W
Switching performance (switching
contact)
Maximum peak inrush-current I
P
(150
μ
s) 400
A
Maximum peak inrush-current I
P
(250
μ
s) 320
A
Maximum peak inrush-current I
P
(600
μ
s) 200
A
Number of electronic ballasts (T5/T8,
single element)
1)
18 W (ABB EVG 1 x 58 CF)
23
24 W (ABB EVG-T5 1 x 24 CY)
23
36 W (ABB EVG 1 x 36 CF)
14
58 W (ABB EVG 1 x 58 CF)
11
80 W (Helvar EL 1 x 80 SC)
10
1)
For multiple element lamps or other types the number of electronic ballasts must be determined using the peak inrush current of the electronic
ballasts.