Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
134
3.2.6.5.1 Parameter window
- Status messages
In this parameter window the
Status messages
are defined.
This parameter is visible if in parameter window
,
enable as fan speeds
with the parameter
Outputs
L, M, N
has been selected.
Enable communication object
"Status byte mode" 1 byte
Options: no
yes
•
yes:
The communication object
Status byte mode
is enabled.
From this status byte the states HEATING, COOLING, automatic, forced
operation and the four limitations are indicated directly via a 1 bit coding.
For further information see:
Status byte fan, forced operation
With option yes a further parameter appears:
Send object value
Options:
no, update only
after a change
after request
after a change or request
•
no, update only
: The status is updated but not sent.
•
after a change:
The status is sent after a change.
•
after request:
The status is sent after a request.
•
after a change or request:
The status is sent after a change or
a request.