ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
171
No.
Function
Object name
Data type
Flags
28
Status byte mode
Fan
noEIS, 1 byte
noDPT
C, R, T
This communication object is enabled if in parameter window
Status messages
the parameter
Enable communication object “Status byte mode" 1 byte
is selected with option
yes
.
The operating state of the fan can be displayed or sent on the bus via this communication
object. It is possible to parameterise if a communication object value is only updated and
not sent, sent on request, or only sent when changed.
Bit
sequence:
76543210
Bit 7: Forced operation
Telegram value 0: inactive
1:
active
Bit 6: Limitation 1
Telegram value 0: inactive
1:
active
Bit 5: Limitation 2
Telegram value 0: inactive
1:
active
Bit 4: Limitation 3
Telegram value 0: inactive
1:
active
Bit 3: Limitation 4
Telegram value 0: inactive
1:
active
Bit 2: Thermostat fault
Telegram value 0: inactive
1:
active
Bit
1: Automatic
Telegram value 0: inactive
1:
active
Bit
0: HEATING/COOLING
Telegram value 0: COOLING
1:
HEATING
Note
Bit 0: If toggling between HEATING and COOLING is undertaken
automatically using control variables, the status HEATING/COOLING is only
switched in bit 0 if a value > 0 is received on the control value.
For further information see:
Status byte fan, forced operation