ABB i-bus
®
KNX
Planning and application
© 2008 ABB STOTZ-KONTAKT GmbH
248
4.5.4
Logic of the
stage switching
The following illustration indicates the logic of a switchover stage for
a Room Master in dependence on the control values and the parameterised
threshold values and hysteresis.
The diagram relates to a three speed fan without parameterised fan
limitations. The fan limitations are only relevant after the fan speed
has been determined and do not change the flow chart.