ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
131
3.2.6.5
Parameter window
L, M, N: Fan (3 x 6 A)
one-level
In this parameter window all settings for the
one-level fan
are undertaken.
This parameter is visible if in parameter window
page 89, the option
enable as fan speeds
with the parameter
Outputs
L, M, N
has been selected.
Fan type
Option: multi-level
one-level
The fan type to be controlled is set with this parameter.
If a fan with up to three speeds is to be controlled, the option multi-level
must be selected.
If a fan with one speed is to be controlled, the option one-level must be
selected.
Fan speed on bus voltage failure
Option: unchanged
OFF
ON
The behaviour of the fan with a bus voltage failure is defined here.
Fan speed on bus voltage recovery
Options: unchanged
OFF
ON
The behaviour of the fan on bus voltage recovery is defined here.
•
unchanged:
The fan speed of the fan remains unchanged.
•
OFF:
The fan is switched off.
•
ON:
The fan is switched on.