Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
98
•
yes:
The following parameter appears:
Automatic reactivation of
automatic control
Options:
no
yes
If automatic control has been deactivated via a telegram to the direct
communication objects, it can be automatically reactivated after the
parameterised time has timed out. This function is also particularly
suitable if no additional button is available for the activation or
deactivation of automatic control.
•
yes:
The following parameter appears:
Automatically reactivate after
in min [10…6,000]
Options: 10…300…6,000
Using this parameter the duration for the automatic reactivation
of the automatic control is defined. If automatic control is inter-
rupted during the parameterised time by a direct communication
object, the parameterised time for automatic reactivation of
automatic control recommences to count from 0 (retriggering).
Note
A change of the parameter value will only become active after the
next deactivation of automatic control.
Position if sun = 1
(sun is shining)
Options: no
reaction
UP
DOWN
STOP
Receive position via 8 bit values
This parameter defines the reaction with sun = 1 (sun is shining) in the
automatic sun screen operation.
•
no reaction: The current movement action is completed.
•
UP
: The shutter moves UP.
•
DOWN:
The shutter moves DOWN.
•
STOP:
The output is electrically disconnected, i.e. a moving shutter is
stopped.
•
Receive position via 8 bit values: The shutter moves to position by
receiving an 8 bit value. For this purpose the communication objects
Sun: Move to position [0…255]
and
Sun: adjust louvres [0…255]
are available.