ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
42
3.2.2.1.3 Special function
Fault monitoring input
Note
For the operating mode
Fault monitoring input
the options must be adapted
in comparison to the standard settings.
The options
Fault monitoring mode
are listed separately in the following.
In this chapter only the parameters which are relevant for optimum
Fault
monitoring input
performance are listed.
All descriptions of the parameter should be taken from parameter window
Debounce time
Options:
Fault
monitoring
option:
10/20/30/50/70/100/150 ms
50 ms
Distinction between short and
long operation
Options:
Fault
monitoring
option:
yes/no
no
Activate minimum signal time
Options:
Fault
monitoring
option:
yes/no
yes
On closing the contact
in value x 0.1 s [1…65,535]
Options:
Fault
monitoring
option:
1…10…65,535
2
On opening the contact
in value x 0.1 s [1…65,535]
Options:
Fault
monitoring
option:
1…10…65,535
2
Note
Depending on the system type, a minimum signal duration of two
seconds should be set. With the evaluation for example of coupling
switches, generator switches or incoming circuit-breakers from
switchgear systems, a smaller minimum signal time of 100 ms for
example, may be necessary.
It is essential to co-ordinate the switching times with the operator!
Smaller signal/switch times may be required depending on the
system.