![ABB i-bus KNX Room Master Premium RM/S 2.1 Скачать руководство пользователя страница 32](http://html.mh-extra.com/html/abb/i-bus-knx-room-master-premium-rm-s-2-1/i-bus-knx-room-master-premium-rm-s-2-1_product-manual_3076032.webp)
ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
30
Rate of telegrams
Options: not
limited
1/2/3/5/10/20
telegrams/second
0.05/0.1/0.2/0.3/0.5 seconds/telegram
•
1/2/3/5/10/20 telegrams/second:
X telegrams per second
are sent.
•
0.05/0.1/0.2/0.3/0.5 seconds/telegram:
A telegram is sent every x
seconds.
Using this parameter the bus load generated by the device can be limited.
Send object “in operation”
Options: no
send value 0 cyclically
send value 1 cyclically
The
in operation
communication object indicates the correct function of the
device on the bus. This cyclic telegram can be monitored by an external
device.
Note
After bus voltage recovery the communication object sends its value after
the set sending and switching delay.
•
send value 0(1) cyclically:
An additional parameter appears:
Sending cycle time in s [1…65,535]
Options: 1…60…65,535
Here a time interval is set which the communication object
In operation
uses to cyclically send a telegram.
Enable communication object
"Request status values" 1 bit
Options: no
yes
•
yes:
A 1 bit communication object
Request status values
is enabled.
Via this communication object all status messages can be requested
provided that they have been parameterised with the option
after a change
or request
.
With option
yes
the following parameters appear: