ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
37
Example: Minimum signal time of the input signal for a detected
edge:
In only two cases, no further edge changes occur within the minimum
signal duration T
M
after a change of edge. For this reason only both of
these are detected as valid.
Scan input after download,
bus reset and bus voltage recovery
Options: no
yes
•
yes:
The object value is scanned after a download, bus reset and bus
voltage recovery.
•
no:
The object value is not scanned after a download, bus reset and bus
voltage recovery.
With option
yes
the following additional parameters appear in the parameter:
Inactive wait state after bus voltage
recovery in s [0…30,000]
Options: 0…30,000
Here the waiting time after a bus voltage recovery is set. After the
waiting time has elapsed the state on the input terminals is scanned.
The input reacts as if the state on the input terminals has just
changed.
Note
The inactive waiting time does not add to the actual, adjustable
send delay time. This can be set separately.
T
M
T
M
Input signal
Detected pulse edge