![ABB i-bus KNX Room Master Premium RM/S 2.1 Скачать руководство пользователя страница 108](http://html.mh-extra.com/html/abb/i-bus-knx-room-master-premium-rm-s-2-1/i-bus-knx-room-master-premium-rm-s-2-1_product-manual_3076108.webp)
ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
106
Status response of position via communication object
“Move to position [0…255]”
Options: no
yes
This parameter defines if the communication object
Move to position/Lamella
[0…255]
sends a status response.
•
yes:
The following parameter appears:
Send object value
Options:
no, update only
after a change
after request
after a change or request
•
no, update only
: The status is updated but not sent.
•
after a change:
The status is sent after a change.
•
after request:
The status is sent after a request.
•
after a change or request:
The status is sent after a change or a
request.
Extra status response
Options: none
end
positions
Status
byte
An additional status response can be enabled with this parameter.
•
none:
There is no feedback.
•
end positions:
The communication objects
Status of lower position
and
Status of upper position
are enabled, these indicate that the shutter/blind
are in the upper or lower position (measured based on total movement
time).
•
Status byte:
The communication object
Status byte
which contains
further information in coded format is enabled.
Enable function automatic
Options: no
yes
•
no:
The parameter window remains disabled and invisible.
•
yes:
The parameter window -
Automatic
appears.
By enabling the function
Automatic
the parameter window -
Automatic
is enabled where further settings can be made.