ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
156
Forced operation on object value
Options: 1
0
Here you set the object value used to forcibly operate the valve.
Valve position on forced operation in %
[0…100]
Options: 0…30…100
Here the forced operation of the valve position in percent is set.
Note
The characteristic curve adjustment is also active with forced
operation.
Enable communication object
“Valve position status”
Options: no
1 bit
1 byte
Note
The valve position status is sent immediately after the control value is
received.
•
1 bit:
The following parameters appear:
Send object value
Options:
no, update only
after a change
after request
after a change or request
•
no, update only
: The status is updated but not sent.
•
after a change:
The status is sent after a change.
•
after request:
The status is sent after a request.
•
after a change or request:
The status is sent after a change or
a request.
Object value with valve position >0
Options: 1
0
•
1 byte:
The following parameter appears: