Fieldbus control 291
Note:
After any changes to the communication settings, protocol must be reactivated
by either cycling the drive power, or by clearing and then restoring the station Id
(5302) or use Reinitialize Device Service.
5313 EFB PAR13
Not used for Comm setup.
This parameter sets the
BACnet Device Object
Max Master Property.
5314 EFB PAR14
Not used for Comm setup.
5315 EFB PAR15
Not used for Comm setup.
5316 EFB PAR 16
Not used for Comm setup.
This parameter indicates
the count of MS/TP tokens
passed to this drive.
5317 EFB PAR17
This parameter works with
parameter 5311 to set
BACnet Device Object
Instance IDs. See
parameter 5311.
Code Description
EFB Protocol Reference
Modbus
N2
FLN
BACnet
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...