366 Fault tracing
5030
Invalid request
Contact your local ABB representative.
5031
Drive is not ready for
operation, eg due to low
DC voltage.
Check input power supply.
5032
Parameter error
Contact your local ABB representative.
5040
Parameter download error.
Selected parameter set is
not in current parameter
backup file.
Perform upload function before download.
5041
Parameter backup file
does not fit into memory.
Contact your local ABB representative.
5042
Parameter download error.
Selected parameter set is
not in current parameter
backup file.
Perform upload function before download.
5043
No start inhibit
5044
Parameter backup file
restoring error
Check that file is compatible with drive.
5050
Parameter upload aborted
Retry parameter upload.
5051
File error
Contact your local ABB representative.
5052
Parameter upload has
failed.
Retry parameter upload.
5060
Parameter download
aborted
Retry parameter download.
5062
Parameter download has
failed.
Retry parameter download.
5070
Panel backup memory
write error
Contact your local ABB representative.
5071
Panel backup memory
read error
Contact your local ABB representative.
5080
Operation is not allowed
because drive is not in
local control mode.
Switch to local control mode.
5081
Operation is not allowed
because of active fault.
Check cause of fault and reset fault.
5083
Operation is not allowed
because parameter lock is
on.
Check parameter
setting.
5084
Operation is not allowed
because drive is
performing task.
Wait until task is completed and retry.
5085
Parameter download from
source to destination drive
has failed.
Check that source and destination drive types
are same, ie, ACS320. See the type
designation label of the drive.
5086
Parameter download from
source to destination drive
has failed.
Check that source and destination drive type
designations are the same. See type
designation labels of the drives.
ALARM CODE CAUSE
WHAT TO DO
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...