184 Actual signals and parameters
1609
START ENABLE 2
-5…7
1
0
Selects the source of the start enable 2 signal.
Note:
Start enable functionality differs from the run enable functionality.
0 = NOT SEL – Allows the drive to start without an external start enable signal.
1 = DI1 – Defines digital input DI1 as the start enable 2 signal. This digital input must
be activated for start enable 2 signal. If the voltage drops and de-activates this
digital input, the drive will coast to stop and show alarm
on the panel display. The drive will not start until start enable 2 signal
resumes.
2…5 = DI2…DI5 – Defines digital input DI2…DI5 as the start enable 2 signal. See DI1
above.
7 = COMM – Assigns the fieldbus Command word as the source for the start enable 2
signal. Bit 3 of the Command word 2 (parameter
) activates the start disable 2
signal. See fieldbus user’s manual for detailed instructions.
-1 = DI1(INV) – Defines an inverted digital input DI1 as the start enable 2 signal.
-2…-5 = DI2(INV)…DI5(INV) – Defines an inverted digital input DI2…DI5 as the start
enable 2 signal.
• See DI1(INV) above.
1610
DISPLAY ALARMS
0, 1
1
1
Controls the visibility of the following alarms:
•
•
•
•
.
For more information, see chapter
.
0 = NO – The above alarms are suppressed.
1 = YES – All of the above alarms are enabled.
1611
PARAMETER VIEW
1…3
1
2
Selects the parameter view, in other words, which parameters are shown.
Note:
This parameter is visible only when it is activated by the optional FlashDrop
device. The FlashDrop is designed for fast copying of parameters to unpowered
drives. It allows fast customization of the parameter list, for example, selected
parameters can be hidden. For more information, see
MFDT-01 FlashDrop User’s
Manual
[3AFE68591074 (English)].
FlashDrop parameter values are activated by setting parameter
to 31 (LOAD FD SET.
1 = FLASHDROP – FlashDrop parameter list is shown. Does not include short
parameter list. Parameters that are hidden by the FlashDrop device are not
visible.
2 = SHORT VIEW – Shows only a subset of all signals and parameters
3 = LONG VIEW – Shows all signals and parameters.
1612
FAN CONTROL
0, 1
1
0
Selects the heat sink fan On/Off control for forcing the cooling fan of the drive
constantly On,
0 = AUTO – Automatic fan control.
1 = ON – Fan is always On.
Group 16: System controls
Code
Description
Range
Resolution
Default
S
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...