320 Fieldbus control
11
DRIVE MWH
The drive's cumulative power consumption in megawatt
hours. This value cannot be reset.
0141
12
RUN TIME
The drive's cumulative run time in hours. This value may
be reset by commanding FLN point 48, RESET RUN
TIME.
0114
13
DC BUS VOLT
The DC bus voltage level of the drive.
0107
14
OUTPUT VOLT
The AC output voltage applied to the motor.
0109
15
PRC PID FBCK
The Process PID feedback signal.
0130
16
PRC PID DEV
The deviation of the Process PID output signal from its
setpoint.
0132
17
MOTOR TEMP
The measured motor temperature as set up in Group 35. 0145
18
ROTATION CNT The motor's cumulative revolution count, in mega-
revolutions.
0142
19
N/A
20
OVRD TIME
1 of the 5 mandatory FLN points required for
compatibility with Siemens control systems. It has no
functionality in the drive application.
None
21
FWD.REV ACT
Indicates the rotational direction of the motor, regardless
of control source (1 = REV, 0 = FWD).
22
FWD.REV CMD Commanded by FLN to change the rotational direction
of the drive.
Parameter 1001 must be set to COMM for FLN to
control the direction of the motor by EXT1.
Parameter 1002 must be set to COMM for FLN to
control the direction of the motor by EXT2.
23
RUN.STOP ACT Indicates the drive's run status, regardless of control
source (1 = RUN, 0 = STOP).
24
RUN.STOP
CMD
Commanded by FLN to start the drive.
Parameter 1001 must be set to COMM for FLN to
control the run state of the drive by EXT1.
Parameter 1002 must be set to COMM for FLN to have
this control.
25
EXT1.2 ACT
Indicates whether External 1 or External 2 is the active
control source (1 = EXT2, 0 = EXT1).
26
EXT1.2 CMD
Commanded by FLN to select External 1 or External 2
as the active control source (1 = EXT2, 0 = EXT1).
Parameter 1102 must be set to COMM for FLN to have
this control.
27
DRIVE READY
Indicates the drive is ready to accept a run command
(1 = READY, 0 = NOTRDY).
28
AT SETPOINT
Indicates the drive has reached its commanded setpoint
(1 = YES, 0 = NO)
29
DAY.NIGHT
1 of the 5 mandatory FLN points required for
compatibility with Siemens control systems. It has no
functionality in the drive application.
None
30
CURRENT LIM
Sets the output current limit of the drive.
2003
31
ACCEL TIME 1
Sets the acceleration time for Ramp 1.
2202
FLN Detailed Point Descriptions
Point
Description
Drive
Parameter
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...