Fault tracing 363
2022
START ENABLE 2
MISSING
bit 5
No Start Enable 2
signal received
Check parameter
settings.
Check digital input connections.
Check fieldbus communication
settings.
2023
EMERGENCY
STOP
bit 6
Drive has received
emergency stop
command and ramps
to stop according to
ramp time defined by
parameter
.
Check that it is safe to continue
operation.
Return emergency stop push button
to normal position.
2025
FIRST START
bit 8
Motor identification
magnetization is on.
This alarm belongs to
normal start-up
procedure.
Wait until drive indicates that motor
identification is completed.
2026
INPUT PHASE
LOSS
bit 9
(programmable fault
function
Intermediate circuit DC
voltage is oscillating
due to missing input
power line phase or
blown fuse.
Alarm is generated
when DC voltage
ripple exceeds 14% of
nominal DC voltage.
Check input power line fuses.
Check for input power supply
imbalance.
Check fault function parameters.
2027
USER LOAD
CURVE
bit 10
Condition defined by
has been valid
longer than half of the
time set by
.
See parameter
.
2028
START DELAY
bit 11
Start delay in progress See parameter
2030
INLET LOW
bit 13
Pressure at pump/fan
inlet too low
Check for a closed valve on the inlet
side of the pump/fan.
Check piping for leaks.
See parameter
2031
OUTLET HIGH
bit 14
Pressure at pump/fan
outlet too high
Check piping for blocks.
See parameter
2032
PIPE FILL
bit 15
Pipe fill in progress
2033
INLET VERY LOW
bit 0
Pressure at pump/fan
inlet too low
Check for a closed valve on the inlet
side of the pump/fan.
Check piping for leaks.
See parameter
CODE
ALARM
CAUSE
WHAT TO DO
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...