254 Actual signals and parameters
7 = DI1/SUP1OVR – Pump cleaning is started by rising edge of digital input DI1 or
SUPRV1 OVER, not both at the same time. See parameter
.
8 = DI2/SUP1OVR – See selection DI1/SUP1OVR.
9 = DI3/SUP1OVR – See selection DI1/SUP1OVR.
10 = DI4/SUP1OVR – See selection DI1/SUP1OVR.
11 = DI5/SUP1OVR – See selection DI1/SUP1OVR.
12 = SUPRV1 OVER – Trigger on SUPRV1 OVER (parameter
). See parameter
13 = DRIVE START – Trigger when the drive receives a start command.
14 = TIMER TRIG – Pump cleaning sequence is started periodically at intervals
-1 = DI1(INV) – Trigger on the falling edge of digital input DI1.
-2 = DI2(INV) – See selection DI1(INV).
-3 = DI3(INV) – See selection DI1(INV).
-4 = DI4(INV) – See selection DI1(INV).
-5 = DI5(INV) – See selection DI1(INV).
-7 = DI1(INV)S1O – Enable on the falling edge of digital input DI1, trigger on SUPRV1
OVER (parameter
.
-8 = DI2(INV)S1O – See selection DI1(INV)S1O.
-9 = DI3(INV)S1O – See selection DI1(INV)S1O.
-10 = DI4(INV)S1O – See selection DI1(INV)S1O.
-11 = DI5(INV)S1O – See selection DI1(INV)S1O.
4602
FWD STEP
0.0 … 100.0%
1 = 0.1%
0.0%
Defines the forward step frequency for the pump cleaning sequence in percent of the
nominal motor frequency (parameter
4603
REV STEP
0.0 … 100.0%
1 = 0.1%
0.0%
Defines the reverse step frequency for the pump cleaning sequence in percent of the
nominal motor frequency (parameter
4604
OFF TIME
0.0 … 1000.0 s
1 = 0.1 s
0.0 s
Defines the length of the interval between forward and reverse steps in the pump
cleaning sequence in seconds.
4605
FWD TIME
0.0 … 1000.0 s
1 = 0.1 s
0.0 s
Defines the duration of each forward step in the pump cleaning sequence in seconds.
4606
REV TIME
0.0 … 1000.0 s
1 = 0.1 s
0.0 s
Defines the duration of each reverse step in the pump cleaning sequence in seconds.
4607
TRIG TIME
0.0 … 200.0 h
1 = 0.1 h
0.0 h
Defines the time for setting TIMER TRIG of parameter
.
4608
COUNT
0…100
1 = 1
0
Number of steps to be performed in the pump cleaning sequence.
Group 46: Pump cleaning
Code
Description
Range
Resolution
Default
S
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...