140 Program features
How to parameterize SPFC control
1. Set PFA reference steps (parameters
) if needed.
2. Set PFA start and stop frequencies (parameters
3. Set PFA auxiliary motor start and stop delays (parameters
…
4. Set the number of auxiliary motors (parameter
).
5. Enable Autochange (parameter
). In SPFC control, the parameter only allows
SPFC to use PFA's alternation switchgear box. It is not used as the operating time
interval between the automatic motor changes as in normal PFA application.
6. Autochange level is ignored (parameter
7. Parameterize Interlocks (parameter
8. Set Bypass function if needed (parameter
).
9. Set PFA start delay (parameter
).
10. Enable SPFC. Depending on the application, set parameter
to value 2 (SPFC ACTIVE – SPFC) or value 3 (SPFC + AUTOCHANGE).
Value 1 (ACTIVE): enables normal PFA functionality.
Value 2 (SPFC ACTIVE – SPFC): enables SPFC function with auxiliary motors
running.
Value 3 (SPFC + AUTOCHANGE): enables SPFC function only when auxiliary
motors are not running
11. Set PFA acceleration and deceleration times if needed (parameters
).
12. Autochange enable with a timed function is ignored (parameter
).
13. Set relays in
. (Transistor output TO [parameter
] can be used as an additional relay output, if needed.) Both PFA and
SPFC use these relays. You must set at least as many relays as there are motors
set for SPFC (= the number of auxiliary motors [parameter
] + 1 [speed
regulated motor] when SPFC is used).
14. Set the number of PFA controlled motors in parameter
(= number of PFC
relays in
15. Also set other needed motor dependent parameters, eg
,
.
PFA control and SPFC control default settings have differences in acceleration time
(
), deceleration time (
) and auxiliary motor stop delay (
) parameters.
Settings
Parameter
Additional information
Selections of relay outputs for starting and stopping of
motors
Selections of relay outputs for starting and stopping of
motor (transistor output can be used as an additional
relay)
Pump protection (pressure monitoring) settings
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...