Actual signals and parameters 191
Group 20: Limits
This group defines minimum and maximum limits to follow in driving the motor –
speed, frequency, current, torque, etc.
Group 20: Limits
Code
Description
Range
Resolution
Default
S
2003
MAX CURRENT
0.0 … 1.1 * I
2N
0.1 A
1.1 * I
2N
Defines the maximum output current (A) supplied by the drive to the motor.
2006
UNDERVOLT CTRL
0…2
1
1
Sets the DC undervoltage controller on or off. When on:
• If the DC bus voltage drops due to loss of input power, the undervoltage controller
decreases the motor speed in order to keep the DC bus voltage above the lower
limit.
• When the motor speed decreases, the inertia of the load causes regeneration back
into the drive, keeping the DC bus charged, and preventing an undervoltage trip.
• The DC undervoltage controller increases power loss ride-through on systems with
a high inertia, such as a centrifuge or a fan.
0 = DISABLE – Disables controller.
1 = ENABLE (TIME) – Enables controller with 500 ms time limit for operation.
2 = ENABLE – Enables controlled without maximum time limit for operation.
2007
MINIMUM FREQ
-500.0 … 500.0 Hz
0.1 Hz
0.0 Hz
Defines the minimum limit for
the drive output frequency.
• A positive or zero minimum
speed frequency defines two
ranges, one positive and one
negative.
• A negative minimum speed
frequency defines one speed
range. See figure.
Note:
Keep MINIMUM
FREQ
≤
MAXIMUM FREQ.
2008
MAXIMUM FREQ
0.0 … 500.0 Hz
0.1 Hz
60.0 Hz
(US)
Defines the maximum limit for the drive output frequency.
Freq
Frequency range allowed
Frequency range allowed
Frequency range allowed
Time
Freq
Time
0
0
-(
-(
value is < 0
value is > 0
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...