286 Fieldbus control
Mechanical and electrical installation – EFB
WARNING!
Connections should be made only while the drive is disconnected
from the power source.
Drive terminals 23…26 are for EIA-485 communications.
• Use Belden 9842 or equivalent. Belden 9842 is a dual twisted, shielded pair cable
with a wave impedance of 120
Ω
.
• Use one of these twisted shielded pairs for the EIA-485 link. Use this pair to
connect all A (-) terminals together and all B (+) terminals together.
• Use one of the wires in the other pair for the logical ground (terminal 26), leaving
one wire unused.
• Do not directly ground the EIA-485 network at any point. Ground all devices on
the network using their corresponding grounding terminals.
• As always, the grounding wires should not form any closed loops, and all the
devices should be grounded to a common ground.
• Connect the EIA-485 link in a daisy-chained bus, without dropout lines.
• To reduce noise on the network, terminate the EIA-485 network using 120
Ω
resistors at both ends of the network. Use jumper J701 to connect or disconnect
the termination resistors. See below wiring diagram. This circuit provides pull-up
active termination resistors.
• For configuration information see the following:
- below.
-
Activate drive control functions – EFB
.
- The appropriate EFB protocol specific technical data. For example,
.
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...