![ABB ACS320 series Скачать руководство пользователя страница 331](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965331.webp)
Fieldbus control 331
BACnet quick-start sequence
The following steps summarize the process for enabling and configuring BACnet on
the ACS320:
1. Enable BACnet protocol: Set drive parameter
BACNET (5).
Note:
If you cannot see the desired selection on the panel, your drive does not
have that protocol software in the application memory.
•
To confirm this selection, read drive parameter
. It
should read x5xx (where “x” is any value).
2. Place the BACnet channel in “reset”: Set drive parameter
= 0.
•
This setting holds the BACnet communication channel in reset while
remaining settings are completed.
3. Define the MS/TP baud rate.
•
Set drive parameter
= appropriate value.
4. Define the Device Object Instance ID.
•
To define a specific device object instance value, use drive parameters 5311
and 5317 (object instance values must be unique and in the range 1 to
4,194,303).
•
To use the drive’s MS/TP MAC ID as the device object instance value, set
drive parameter 5311 and 5317 = 0.
5. Define a unique MS/TP MAC ID. Set drive parameter
appropriate value.
•
Once this parameter is set to a non-zero value, current BACnet settings are
“latched” and used for communication until the channel is reset.
•
In order to participate in MS/TP token passing, the MAC ID used must be
within the limits defined by other masters’ “Max Master” property.
6. Confirm proper BACnet communication.
•
When BACnet communication is operating properly, drive parameter 5316
EFB PAR 16 (the MS/TP token counter), should be continually increasing.
•
Drive parameter
, should be stable.
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...