![ABB ACS320 series Скачать руководство пользователя страница 169](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965169.webp)
Actual signals and parameters 169
Group 12: Constant speeds
Code
Description
Range
Resolution
Default
S
1201
CONST SPEED SEL
-13…19
1
3
Defines the digital inputs used to select Constant speeds. See general comments in
the introduction.
0 = NOT SEL – Disables the constant speed function.
1 = DI1 – Selects Constant speed 1 with digital input 1.
• Digital input activated = Constant speed 1 activated.
2…5 = DI2…DI5 – Selects Constant speed 1 with digital input DI2…DI5.
7 = DI1,2 – Selects one of three Constant speeds (1…3) using DI1 and DI2.
• Uses two digital inputs, as defined below (0 = DI de-activated, 1 = DI activated):
• Can be set up as a so-called fault speed, which is activated if the control signal is
and parameter
8 = DI2,3 – Selects one of three Constant speeds (1…3) using DI2 and DI3.
• See DI1,2 for code.
9 = DI3,4 – Selects one of three Constant speeds (1…3) using DI3 and DI4.
• See DI1,2 for code.
10 = DI4,5 – Selects one of three Constant speeds (1…3) using 4 and 5.
• See DI1,2 for code.
12 = DI1,2,3 – Selects one of seven Constant speeds (1…7) using DI1, DI2 and DI3.
• Uses three digital inputs, as defined below (0 = DI de-activated, 1 = DI activated):
13 = DI3,4,5 – Selects one of seven Constant speeds (1…7) using DI3, DI4 and DI5.
• See DI1,2,3 for code.
DI1
DI2
Function
0
0
No constant speed
1
0
Constant speed 1 (1202)
0
1
Constant speed 2 (1203)
1
1
Constant speed 3 (1204)
DI1
DI2
DI3
Function
0
0
0
No constant speed
1
0
0
Constant speed 1 (1202)
0
1
0
Constant speed 2 (1203)
1
1
0
Constant speed 3 (1204)
0
0
1
Constant speed 4 (1205)
1
0
1
Constant speed 5 (1206)
0
1
1
Constant speed 6 (1207)
1
1
1
Constant speed 7 (1208)
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...