174 Actual signals and parameters
Group 14: Relay outputs
This group defines the condition that activates each of the relay outputs.
Group 14: Relay outputs
Code
Description
Range
Resolution
Default
S
1401
RELAY OUTPUT 1
0…69
1
1
Defines the event or condition that activates relay 1 – what relay output 1 means.
0 = NOT SEL – Relay is not used and is de-energized.
1 = READY – Energize relay when drive is ready to function. Requires:
• Run enable signal present.
• No faults exist.
• Supply voltage is within range.
• Emergency Stop command is not on.
2 = RUN – Energize relay when the drive is running.
3 = FAULT (-1) – Energize relay when power is applied. De-energizes when a fault
occurs.
4 = FAULT – Energize relay when a fault is active.
5 = ALARM – Energize relay when an alarm is active.
6 = REVERSED – Energize relay when motor rotates in reverse direction.
7 = STARTED – Energize relay when drive receives a start command (even if Run
Enable signal is not present). De-energized relay when drive receives a stop
command or a fault occurs.
8 = SUPRV1 OVER – Energize relay when first supervised parameter (
) exceeds
the limit (
• See
.
9 = SUPRV1 UNDER – Energize relay when first supervised parameter (
) drops
below the limit (
• See
.
10 = SUPRV2 OVER – Energize relay when second supervised parameter (
exceeds the limit (
).
• See
.
11 = SUPRV2 UNDER – Energize relay when second supervised parameter (
drops below the limit (
).
• See
.
12 = SUPRV3 OVER – Energize relay when third supervised parameter (
exceeds the limit (
).
• See
.
13 = SUPRV3 UNDER – Energize relay when third supervised parameter (
)
drops below the limit (
).
• See
.
14 = AT SET POINT – Energize relay when the output frequency is equal to the
reference frequency.
15 = FAULT (RST) – Energize relay when the drive is in a fault condition and will reset
after the programmed auto-reset delay.
• See parameter
16 = FLT/ALARM – Energize relay when fault or alarm occurs.
17 = EXT CTRL – Energize relay when external control is selected.
18 = REF 2 SEL – Energize relay when EXT2 is selected.
19 = CONST FREQ– Energize relay when a constant speed is selected.
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...