Actual signals and parameters 211
LO
>
HI
Operating data
supervision using relay
outputs, when LO > HI.
The lowest limit (HI
is active initially, and
remains active until the
supervised parameter
goes above the highest
limit (LO
), making
that limit the active limit.
That limit remains active
until the supervised
parameter goes below
the lowest limit (HI
),
making that limit active.
• Case A = Parameter
(or
, etc.)
value is SUPRV1 OVER or SUPRV2 OVER. Initially the relay is de-energized. It is
energized whenever the supervised parameter goes above the active limit.
(or
, etc.)
value is SUPRV1 UNDER or SUPRV2 UNDER. Initially the relay is energized. It is
de-energized whenever the supervised parameter goes below the active limit.
Note:
Case LO > HI represents a special hysteresis with two separate supervision
limits.
3202
SUPERV 1 LIM LO
Depends on selection
-
60.0
Sets the low limit for the first supervised parameter. See parameter
above. Supervision wakes up if the value is below the limit.
3203
SUPERV 1 LIM HI
Depends on selection
-
60.0
Sets the high limit for the first supervised parameter. See parameter
above. Supervision wakes up if the value is above the limit.
3204
SUPERV 2 PARAM
101…178
1
104
Selects the second supervised parameter. See parameter
above.
3205
SUPERV 2 LIM LO
Depends on selection
4.5
Sets the low limit for the second supervised parameter. See parameter
above. Supervision wakes up if the value is below the limit.
3206
SUPERV 2 LIM HI
Depends on selection
4.5
Sets the high limit for the second supervised parameter. See parameter
above. Supervision wakes up if the value is above the limit.
3207
SUPERV 3 PARAM
101…178
1
105
Selects the third supervised parameter. See parameter
above.
Group 32: Supervision
Code
Description
Range
Resolution
Default
S
LO (3202)
t
HI (3203)
Value of supervised parameter
Case A
0
Energized (1)
0
t
t
Case B
Energized (1)
Active limit
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...