384 Technical data
Ratings
Note
: When choke is not used, input current is effected by supply network and
impedance.
Use the table in
Fuses and alternate short-circuit protection
(page
) to correctly
size the input cabling as well as input fuses or MMP for branch circuit protection.
Sizing will be determined by the actual input current which is dependent on the input
line voltage and the input choke selection and rated motor current. If motor rated
current is below I
2N
, I
1N
is reduced relatively.
Type code
Input
Output
Frame
size
without choke
or reactor
with choke or
5% reactor
ACS320-
I
1N
I
1N
(480 V)
I
1N
I
1N
(480 V)
I
LD
2)
I
2N
I
2max
3)
P
N
x = E/U
1)
A
A
A
A
A
A
A
kW
hp
1-phase supply voltage 200…240 V units
(Confirm output ratings meet motor requirements)
01x-02A4-2
6.1
-
4.5
-
2.3
2.4
4.0
0.37
0.5
R0
01x-04A7-2
11.4
-
8.1
-
4.5
4.7
7.9
0.75
1
R1
01x-06A7-2
16.1
-
11.0
-
6.5
6.7
11.4
1.1
1.5
R1
01x-07A5-2
16.8
-
12.0
-
7.2
7.5
12.6
1.5
2
R2
01x-09A8-2
21.0
-
15.0
-
9.4
9.8
16.5
2.2
3
R2
3-phase supply voltage 200
…
240 V units
03x-02A6-2
4.7
-
2.6
-
2.4
2.6
4.2
0.37
0.5
R0
03x-03A9-2
6.7
-
3.9
-
3.5
3.9
6.1
0.55
0.75
R0
03x-05A2-2
8.4
-
5.2
-
4.7
5.2
8.2
0.75
1
R1
03x-07A4-2
13.0
-
7.4
-
6.7
7.4
11.7
1.1
1.5
R1
03x-08A3-2
13.2
-
8.3
-
7.5
8.3
13.1
1.5
2
R1
03x-10A8-2
15.7
-
10.8
-
9.8
10.8
17.2
2.2
3
R2
03x-14A6-2
23.9
-
14.6
-
13.3
14.6
23.3
3
3
R2
03x-19A4-2
27.3
-
19.4
-
17.6
19.4
30.8
4
5
R2
03x-26A8-2
45.0
-
26.8
-
24.4
26.8
42.7
5.5
7.5
R3
03x-34A1-2
55.0
-
34.1
-
31.0
34.1
54.3
7.5
10
R4
03x-50A8-2
76.0
-
50.8
-
46.2
50.8
80.9
11.0
15
R4
3-phase supply voltage 380
…
480 V units
03x-01A2-4
2.4
2.0
1.3
1.1
1.1
1.2
2.1
0.37
0.5
R0
03x-01A9-4
4.0
3.3
2.0
1.7
1.7
1.9
3.3
0.55
0.75
R0
03x-02A4-4
4.5
3.8
2.5
2.1
2.2
2.4
4.2
0.75
1.0
R1
03x-03A3-4
6.6
5.5
3.5
2.9
3.0
3.3
5.8
1.1
1.5
R1
03x-04A1-4
7.6
6.3
3.8
3.2
3.7
4.1
7.2
1.5
2.0
R1
03x-05A6-4
10.6
8.8
5.3
4.4
5.1
5.6
9.8
2.2
3.0
R1
03x-07A3-4
12.8
10.7
6.8
5.7
6.6
7.3
12.8
3.0
3.0
R1
03x-08A8-4
15.0
12.5
8.6
7.2
8.0
8.8
15.4
4.0
5.0
R1
03x-12A5-4
20.7
17.2
12.3
10.3
11.4
12.5
21.9
5.5
7.5
R3
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...