Fault tracing 365
Alarms generated by the Basic control panel
The Basic control panel indicates control panel alarms with a code, A5xxx.
ALARM CODE CAUSE
WHAT TO DO
5001
Drive is not responding.
Check panel connection.
5002
Incompatible
communication profile
Contact your local ABB representative.
5010
Corrupted panel parameter
backup file
Retry parameter upload.
Retry parameter download.
5011
Drive is controlled from
another source.
Change drive control to local control mode.
5012
Direction of rotation is
locked.
Enable change of direction. See parameter
.
5013
Panel control is disabled
because start inhibit is
active.
Start from the panel is not possible. Reset the
emergency stop command or remove the 3-wire
stop command before starting from the panel.
See parameters
and
5014
Panel control is disabled
because of drive fault.
Reset drive fault and retry.
5015
Panel control is disabled
because local control
mode lock is active.
Deactivate local control mode lock and retry.
See parameter
.
5018
Parameter default value is
not found.
Contact your local ABB representative.
5019
Writing non-zero
parameter value is
prohibited.
Only parameter reset is allowed.
5020
Parameter or parameter
group does not exist or
parameter value is
inconsistent.
Contact your local ABB representative.
5021
Parameter or parameter
group is hidden.
Contact your local ABB representative.
5022
Parameter is write
protected.
Parameter value is read-only and cannot be
changed.
5023
Parameter change is not
allowed, when drive is
running.
Stop drive and change parameter value.
5024
Drive is executing task.
Wait until task is completed.
5025
Software is being uploaded
or downloaded.
Wait until upload/download is complete.
5026
Value is at or below
minimum limit.
Contact your local ABB representative.
5027
Value is at or above
maximum limit.
Contact your local ABB representative.
5028
Invalid value
Contact your local ABB representative.
5029
Memory is not ready.
Retry.
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...