Actual signals and parameters 251
Group 45: Energy saving
This group defines the set-up for calculation and optimization of energy savings.
Note:
The values of saved energy parameters
,
are derived from subtracting the drive's energy consumed from the direct-on-line
(DOL) consumption calculated on the basis of parameter
. As
such, the accuracy of the values is dependent on the accuracy of the power estimate
entered in that parameter.
4425
PID ENABLE DEV
0.0 … 100.0%
1 = 0.1%
0.1%
Defines the level when the Precharge function is disabled and PID is enabled. When
the level is reached, PID is enabled. PID is executed as parameterized. If reference
ramp times are set, they are used.
• Value in percent of the maximum feedback.
4426
PIPEFILL TIMEOUT
1 … 60000 s
1 = 1 s
NOT SEL
Defines the maximum time the Precharge function is allowed to operate. If this time
elapses, PID is preset and PID is allowed to run as it is parameterized – with or without
reference ramps.
0 = NOT SEL - 1…60000 s: Max. Precharge operating time
Group 45: Energy saving
Code
Description
Range
Resolution
Default
S
4501
ENERGY
OPTIMIZER
OFF
Enables or disables the energy optimizer, which optimizes the flux so that the total
energy consumption and motor noise level are reduced when the drive operates below
the nominal load. The total efficiency (motor and drive) can be improved by 1…10%
depending on load torque and speed.
0 = OFF – Disabled.
1 = ON – Enabled.
4502
ENERGY PRICE
0.00 … 655.35
1 = 0.1
(Currency)
0.00
(Currency)
Price of energy per kWh. Used for reference when energy savings are calculated. See
parameters
,
,
and
(reduction in carbon dioxide emissions in
tn).
4507
CO2 CONV FACTOR
0.0 … 10.0 tn/MWh
1 = 0.1
tn/MWh
0.5 tn/MWh
Conversion factor for converting energy into CO2 emissions (kg/kWh or tn/MWh).
Used for multiplying the saved energy in MWh to calculate the value of parameter
(reduction in carbon dioxide emissions in tn).
Group 44: Pump protection
Code
Description
Range
Resolution
Default
S
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...