252 Actual signals and parameters
4508
PUMP POWER
0.0 … 1000.0%
1 = 0.1%
100.0%
Pump power when connected directly to supply (DOL). Used for reference when
energy savings are calculated. See parameters
,
and
It is possible to use this parameter as the reference power also for other applications
than pumps. The reference power can also be some other constant power than a
motor connected directly on-line.
4509
ENERGY RESET
DONE
Resets energy calculators
,
and
.
0 = DONE – Reset not requested (normal operation).
1 = RESET – Reset energy counters. The value reverts automatically to DONE.
Group 45: Energy saving
Code
Description
Range
Resolution
Default
S
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...