Actual signals and parameters 161
5 = DI1P, 2P, 3P – Start Forward, Start Reverse, and Stop.
• Start and Direction commands are given simultaneously with two separate
momentary push-buttons (the P stands for “pulse”).
• Start Forward command is through a normally open push-button connected to
digital input DI1. To start the drive, the digital input DI3 must be activated during
the pulse in DI1.
• Start Reverse command is through a normally open push-button connected to
digital input DI2. To start the drive, the digital input DI3 must be activated prior the
pulse in DI2.
• Connect multiple Start push-buttons in parallel.
• Stop is through a normally closed push-button connected to digital input DI3.
• Connect multiple Stop push-buttons in series.
• Requires parameter
= 3 (REQUEST).
8 = KEYPAD – Control Panel.
• Start/Stop and Direction commands are through the control panel when EXT1 is
active.
• Direction control requires parameter
= 3 (REQUEST).
9 = DI1F, 2R – Start/Stop/Direction commands through DI1 and DI2 combinations.
• Start forward = DI1 activated and DI2 de-activated.
• Start reverse = DI1 de-activated and DI2 activated.
• Stop = both DI1 and DI2 activated, or both de-activated.
• Requires parameter
= 3 (REQUEST).
10 = COMM – Assigns the fieldbus Command word as the source for the start/stop
and direction commands.
• Bits 0,1, 2 of Command word 1 (parameter
) activates the
start/stop and direction commands.
• See Fieldbus user’s manual for detailed instructions.
11 = TIMER 1 – Assigns Start/Stop control to Timer 1 (Timer activated = START;
Timer de-activated = STOP). See
.
12…14 = TIMER 2… 4 – Assigns Start/Stop control to Timer 2…4.
See Timer Function 1 above.
20 = DI5 – Start and stop through digital input DI5. 0 = stop, 1 = start. Direction is fixed
according to parameter
(setting REQUEST = FORWARD).
21 = DI5, 4 – Start and stop through digital input DI5. 0 = stop, 1 = start. Direction
through digital input DI4. 0 = forward, 1 = reverse. To control direction, parameter
must be REQUEST.
27 = SUPRV1 OVER – Start when the value of supervision parameter 1 goes over the
supervision high limit. Stop when the value goes below the low limit. See
28 = SUPRV1 UNDER – Start when the value of the supervision parameter 1 goes
below the supervision low limit. Stop when the value goes over the high limit. See
29 = SUPRV2 OVER – See selection SUPRV1 OVER.
30 = SUPRV2 UNDER – See selection SUPRV1 UNDER.
31 = SUPRV3 OVER – See selection SUPRV1 OVER.
32 = SUPRV3 UNDER – See selection SUPRV1 UNDER.
33 = SDI2 – Start and stop as for SUPRV1 OVER. Direction through
digital input DI2. 0 = forward, 1 = reverse. To control direction, parameter
setting must be REQUEST.
34 = SUP1 UDR+DI2 – Start and stop as for SUPRV1 UNDER. Direction through
digital input DI2. 0 = forward, 1 = reverse. To control direction, parameter
setting must be REQUEST.
Group 10: Start/Stop/Dir
Code
Description
Range
Resolution
Default
S
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...