Actual signals and parameters 257
5305
EFB CTRL PROFILE
0…2
1
0
Selects the communication profile. See section
on page
.
0 = ABB DRV LIM – Operation of Control/Status words conforms to ABB Drives Profile.
1 = DCU PROFILE –
Operation of Control/Status words conforms to 32-bit DCU
Profile.
2 = ABB DRV FULL – Operation of Control/Status words conforms to ABB Drives
Profile.
5306
EFB OK MESSAGES
0…65535
1
0
Number of valid messages received by the drive. During normal operation, this number
increases constantly.
5307
EFB CRC ERRORS
0…65535
1
0
Number of messages with a CRC (cyclic redundancy check) error received by the
drive. If the number is high, check CRC calculation for possible errors.
Note:
High electromagnetic noise levels generate errors.
5308
EFB UART ERRORS
0…65535
1
0
Number of messages with a character error received by the drive.
5309
EFB STATUS
0…7
1
0
Status of the EFB protocol.
0 = IDLE – EFB protocol is configured, but not receiving any messages.
1 = EXECUT INIT – EFB protocol is initializing.
2 = TIME OUT – A time-out has occurred in the communication between the network
master and the EFB protocol.
3 = CONFIG ERROR – EFB protocol has a configuration error.
4 = OFF-LINE – EFB protocol is receiving messages that are NOT addressed to this
drive.
5 = ON-LINE – EFB protocol is receiving messages that are addressed to this drive.
6 = RESET– EFB protocol is performing a hardware reset.
7 = LISTEN ONLY – EFB protocol is in listen-only mode.
5310…
5320
EFB PAR 10
…
EFB PAR 20
0…9999
1
Protocol
dep.
5321
MDB DATA IN 1
0…9999
1
0
Modbus register 40013 - Read only. Supported by STD Modbus only.
5322
MDB DATA IN 2
0…9999
1
0
Modbus register 40014 - Read only. Supported by STD Modbus only.
5323
MDB DATA OUT 1
0…9999
1
0
Modbus register 40080 - Write only. Supported by STD Modbus only.
5324
MDB DATA OUT 2
0…9999
1
0
Modbus register 40081 - Write only. Supported by STD Modbus only.
5325
MDB DATA OUT 13
0…9999
1
0
Modbus register 40082 - Write only. Supported by STD Modbus only.
5326
MDB DATA OUT 4
0…9999
1
0
Modbus register 40083 - Write only. Supported by STD Modbus only.
Group 53: EFB protocol
Code
Description
Range
Resolution
Default
S
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...