Actual signals and parameters 269
8119
AUTOCHNG LEVEL
0.0 … 100.0%
0.1%
50.0%
Sets an upper limit, as a percent of output capacity, for the autochange logic. When the
output from the PID/PFA control block exceeds this limit, the Autochange function is
prevented. For example, use this parameter to deny the Autochange function when the
Pump-Fan system is operating near maximum capacity.
Autochange overview
The purpose of the autochange operation is to equalize duty time between multiple
motors used in a system. At each autochange operation:
• A different motor takes a turn connected to the ACS320 output – the speed regu-
lated motor.
• The starting order of the other motors rotates.
The Autochange function requires:
• External switchgear for changing the drive’s output power connections.
• Parameter
= value > 0.
The Autochange function is performed when:
• The running time since the previous autochange operation reaches the time set by
• The PFA input is below the level set by this parameter,
.
Note:
The ACS320 always coasts to stop when autochange operation is performed.
In an autochange operation, the Autochange function does all of the following (see the
figure below):
• Initiates a change when the
running time, since the last
autochange operation,
reaches
, and PFA input is
below limit 8119
AUTOCHNG LEVEL.
• Stops the speed regulated
motor.
• Switches off the contactor
of the speed regulated
motor.
• Increments the starting
order counter, to change
the starting order for the
motors.
• Identifies the next motor in
line to be the speed regulated motor.
• Switches off the above motor’s contactor, if the motor was running. Any other run-
ning motors are not interrupted.
• Switches on the contactor of the new speed regulated motor. The autochange
switchgear connects this motor to the ACS320 power output.
• Delays motor start for the time
Group 81: PFA control
Code
Description
Range
Resolution
Default
S
t
B
PID Output
100%
1PFA
2PFA
3PFA
4PFA
4PFA
2PFA
3PFA
A
– autochange
operation not allowed.
B = Autochange operation occurs.
1PFA, etc. = PID output associated with each motor.
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...