180 Actual signals and parameters
1602
PARAMETER LOCK
0…2
1
1
Determines if the control panel can change parameter values.
• This lock does not limit parameter changes made by macros.
• This lock does not limit parameter changes written by fieldbus inputs.
• This parameter value can be changed only if the correct pass code is entered. See
parameter
.
0 = LOCKED – You cannot use the control panel to change parameter values.
• The lock can be opened by entering the valid pass code to parameter
1 = OPEN – You can use the control panel to change parameter values.
2 = NOT SAVED – You can use the control panel to change parameter values, but
they are not stored in permanent memory.
to 1 (SAVE) to store changed parameter
values to memory.
1603
PASS CODE
0…65535
1
0
Entering the correct pass code allows you to change the parameter lock.
• See parameter
above.
• Code 358 allows you to change the value of the parameter
once.
This entry reverts back to 0 automatically.
1604
FAULT RESET SEL
-5…7
1
0
Selects the source for the fault reset signal. The signal resets the drive after a fault trip
if the cause of the fault no longer exists.
0 = KEYPAD – Defines the control panel as the only fault reset source.
• Fault reset is always possible with control panel.
1 = DI1 – Defines digital input DI1 as a fault reset source.
• Activating the digital input resets the drive.
2…5 = DI2…DI5 – Defines digital input DI2…DI5 as a fault reset source.
• See DI1 above.
7 = START/STOP – Defines the Stop command as a fault reset source.
• Do not use this option when fieldbus communication provides the start, stop and
direction commands.
8 = COMM – Defines the fieldbus as a fault reset source.
• The Command word is supplied through fieldbus communication.
• The bit 4 of the Command word 1 (parameter
) resets the
drive.
-1 = DI1(INV) – Defines an inverted digital input 1 as a fault reset source.
• De-activating the digital input resets the drive.
-2…-5 = DI2(INV)…DI5(INV) – Defines an inverted digital input DI2…DI5 as a fault
reset source.
• See DI1(INV) above.
Group 16: System controls
Code
Description
Range
Resolution
Default
S
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...