Fieldbus control
238
SYSTEM CONTROL INPUTS
COMM.CW
Enables the control of the Run Enable signal through fieldbus 03.01 Main
Control Word bit 3.
Note:
Must be set to YES when the Generic Drive communication profile is
selected (see Par.
).
COMM.CW
Enables fault reset through fieldbus 03.01 Main Control Word bit 7.
Note:
Reset through fieldbus Control Word (03.01 bit 7) is enabled
automatically and it is independent of parameter
setting if parameter
is set to COMM.CW.
DONE; SAVE
Saves parameter value changes (including those made through fieldbus
control) to permanent memory.
COMMUNICATION FAULT FUNCTIONS
FAULT
NO
Determines drive action in case fieldbus communication is lost.
Note:
The communication loss detection is based on monitoring of
received Main and Auxiliary data sets (whose sources are selected with
parameters 90.04 and 90.05 respectively).
0.1 … 60.0 s
Defines the time between Main Reference data set loss detection and the
action selected with parameter 30.18.
0.0 … 60.0 s
Defines the time between Auxiliary Reference data set loss detection and
the action selected with parameter 30.18.
Note:
This supervision function is disabled if this parameter, or parameters
90.01, 90.02 and 90.03 are set to 0.
FIELDBUS REFERENCE TARGET SELECTION
0 … 8999
Defines the drive parameter into which the value of fieldbus reference
REF3 is written.
Format:
xxyy
, where
xx
= parameter group (10 to 89),
yy
= parameter
Index. For example,
3001
= parameter 30.01.
0 … 8999
Defines the drive parameter into which the value of fieldbus reference
REF4 is written.
Format:
see parameter 90.01.
0 … 8999
Defines the drive parameter into which the value of fieldbus reference
REF5 is written.
Format:
see parameter 90.01.
0 … 8999
Defines the drive parameter into which the value of fieldbus reference
REF6 is written.
Format:
see parameter 90.01.
0 … 8999
Defines the drive parameter into which the value of fieldbus reference
REF7 is written.
Format:
see parameter 90.01.
Parameter
Setting for
fieldbus control
Function/Information
Содержание ACS 800 Series
Страница 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Страница 4: ......
Страница 26: ...Start up and control through the I O interface 26 ...
Страница 36: ...Quick start up guide 36 ...
Страница 52: ...Control panel 52 ...
Страница 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Страница 126: ...Program features 126 The figures below show speed limits according to different load conditions ...
Страница 128: ...Program features 128 ...
Страница 150: ...Application macros control location EXT1 EXT2 150 ...
Страница 228: ...Actual signals and parameters 228 ...
Страница 299: ...Adaptive Programming examples for crane control 299 ...
Страница 305: ...Adaptive Programming examples for crane control 305 ...
Страница 312: ...Adaptive Programming examples for crane control 312 The following figures show the previous example enlarged ...
Страница 314: ...Adaptive Programming examples for crane control 314 The following figures show the previous example enlarged ...
Страница 318: ...Analogue Extension Module 318 ...
Страница 332: ...Additional data actual signals and parameters 332 ...
Страница 333: ...DriveWindow 333 DriveWindow DriveWindow connected to the ACS800 RMIO RDCO board and channel CH3 ...
Страница 334: ...DriveWindow 334 ...
Страница 335: ...Control block diagrams 335 Control block diagrams ...
Страница 336: ...Control block diagrams 336 ...
Страница 337: ...Control block diagrams 337 ...
Страница 338: ...Control block diagrams 338 ...
Страница 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...