Actual signals and parameters
192
30.16
MOTOR PHASE
LOSS
Activates the Motor phase loss supervision function.
NO
Inactive
0
FAULT
Active. The drive trips on a fault.
65535
30.17
EARTH FAULT
Selects how the drive reacts when an earth fault is detected in the motor or the
motor cable. See section
on page
WARNING
The drive generates a warning.
0
FAULT
The drive trips on a fault.
65535
30.18
COMM FLT FUNC
Selects how the drive reacts in a fieldbus communication break, that is when
the drive fails to receive the Main Reference Data Set or the Auxiliary
Reference Data Set. The time delays are given with parameters
and
FAULT
Protection is active. The drive trips on a fault and stops the motor as defined
with parameter
1
NO
Protection is inactive.
2
30.19
MAIN REF DS T-OUT Defines the time delay for the Main Reference data set supervision. See
parameter
0.1 … 60.0 s
Time delay
10 … 6000
30.21
AUX DS T-OUT
Defines the delay time for the Auxiliary Reference data set supervision. See
parameter
. The drive automatically activates the supervision 60 seconds
after power switch-on if the value is other than zero.
Note:
The supervision can be displayed by setting the value to 0.
0.0 … 60.0 s
Time delay. 0.0 s = The function is inactive.
0 … 6000
30.22
IO CONFIG FUNC
Selects how the drive reacts in case an optional input or output channel has
been selected as a signal interface, but the communication to the appropriate
analogue or digital I/O extension module has not been set up accordingly in
parameter group
.
Example:
The supervision function wakes up if parameter
is set to DI7,
but
is set to NO.
NO
Inactive.
1
WARNING
Active. The drive generates a warning.
2
30.23
LIMIT WARNING
Activates/deactivates limit alarms INV CUR LIM, DC BUS LIM, MOT CUR LIM,
MOT TORQ LIM and/or MOT POW LIM. For more information, see chapter
.
0...255
Value in decimal. As default none of the alarms are active, that is, the
parameter value is 0.
bit 0 INV_CUR_LIM_IND
bit 1 DC_VOLT_LIM_IND
bit 2 MOT_CUR_LIM_IND
bit 3 MOT_TORQ_LIM_IND
bit 4 MOT_POW_LIM_IND
Example:
When parameter value is set to 3 (bit 0 and 1 values are 1), alarms
INV CUR LIM and DC BUS LIM are active.
-
30.24
EXT FAULT PTR
Defines the source or constant for selection PAR 30.24 of parameter
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value. See parameter
for information on
the difference.
-
Index
Name/Selection
Description
FbEq
Содержание ACS 800 Series
Страница 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Страница 4: ......
Страница 26: ...Start up and control through the I O interface 26 ...
Страница 36: ...Quick start up guide 36 ...
Страница 52: ...Control panel 52 ...
Страница 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Страница 126: ...Program features 126 The figures below show speed limits according to different load conditions ...
Страница 128: ...Program features 128 ...
Страница 150: ...Application macros control location EXT1 EXT2 150 ...
Страница 228: ...Actual signals and parameters 228 ...
Страница 299: ...Adaptive Programming examples for crane control 299 ...
Страница 305: ...Adaptive Programming examples for crane control 305 ...
Страница 312: ...Adaptive Programming examples for crane control 312 The following figures show the previous example enlarged ...
Страница 314: ...Adaptive Programming examples for crane control 314 The following figures show the previous example enlarged ...
Страница 318: ...Analogue Extension Module 318 ...
Страница 332: ...Additional data actual signals and parameters 332 ...
Страница 333: ...DriveWindow 333 DriveWindow DriveWindow connected to the ACS800 RMIO RDCO board and channel CH3 ...
Страница 334: ...DriveWindow 334 ...
Страница 335: ...Control block diagrams 335 Control block diagrams ...
Страница 336: ...Control block diagrams 336 ...
Страница 337: ...Control block diagrams 337 ...
Страница 338: ...Control block diagrams 338 ...
Страница 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...