Actual signals and parameters
216
95 HARDWARE SPECIF
Fan speed control, sine filter application etc.
95.01
FAN SPD CTRL
MODE
Selects the speed control of the optional inverter cooling fan.
CONST 50 Hz
Fan is running at constant frequency of 50 Hz when powered.
0
RUN/STOP
Drive stopped: Fan is running at constant frequency of 10 Hz.
Drive running: Fan is running at constant frequency of 50 Hz.
1
CONTROLLED
The speed of the fan is determined from IGBT temperature vs. fan speed
curve.
2
95.02
FUSE SWITCH CTRL Activates the inverter DC switch (switch fuse) monitoring function. The
monitoring must be active when the Switch Fuse Control Board (ASFC) is in
use and connected to the inverter AINT board, that is in all frame R8i inverters
equipped with the DC switch. The function must be inactive in units that do not
use the ASFC board with the DC switch, that is for frame R2i…R7i inverters
and all single drive units where no DC switch exists. The default setting (ON or
OFF) for each unit is set accordingly at the factory as default.
ACS800 IGBT pulses are always blocked when the program detects that the
DC switch is opened or inverter charging is ongoing (at power switch on). The
application program generates alarm INV DISABLED if the DC switch is
opened when the inverter is stopped. The inverter trips to fault INV DISABLED
if the DC switch is opened when the inverter is running.
OFF
Inactive
0
ON
Active
1
95.03
INT CONFIG USER
Number of parallel connected inverter modules. Activates the Reduced run
function. See section
on page
1...12
Number of parallel connected inverter modules
95.04
EX/SIN REQUEST
Activates the sine filter or Ex-motor application.
NO
Inactive
1
EX
Ex-motor application. Used with motors which comply with the ATEX directive. 2
SIN
Sine filter application. See
Sine Filters User’s Manual for ACS800 Drives
[3AFE68389178 (English)].
3
EX&SIN
EX-motor and sine filter applications. See
Sine Filters User’s Manual for
ACS800 Drives
[3AFE68389178 (English)].
4
95.05
ENA INC SW FREQ
Activates the minimum switching frequency limitation for Ex-motor
applications. Parameter is visible if parameter
EX/SIN REQUEST is set
to EX.
NO
Inactive
0
YES
Active. Minimum switching frequency limit is set to 2 kHz. Used with motors
with an ATEX certification based on 2 kHz minimum switching frequency.
1
Index
Name/Selection
Description
FbEq
Содержание ACS 800 Series
Страница 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Страница 4: ......
Страница 26: ...Start up and control through the I O interface 26 ...
Страница 36: ...Quick start up guide 36 ...
Страница 52: ...Control panel 52 ...
Страница 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Страница 126: ...Program features 126 The figures below show speed limits according to different load conditions ...
Страница 128: ...Program features 128 ...
Страница 150: ...Application macros control location EXT1 EXT2 150 ...
Страница 228: ...Actual signals and parameters 228 ...
Страница 299: ...Adaptive Programming examples for crane control 299 ...
Страница 305: ...Adaptive Programming examples for crane control 305 ...
Страница 312: ...Adaptive Programming examples for crane control 312 The following figures show the previous example enlarged ...
Страница 314: ...Adaptive Programming examples for crane control 314 The following figures show the previous example enlarged ...
Страница 318: ...Analogue Extension Module 318 ...
Страница 332: ...Additional data actual signals and parameters 332 ...
Страница 333: ...DriveWindow 333 DriveWindow DriveWindow connected to the ACS800 RMIO RDCO board and channel CH3 ...
Страница 334: ...DriveWindow 334 ...
Страница 335: ...Control block diagrams 335 Control block diagrams ...
Страница 336: ...Control block diagrams 336 ...
Страница 337: ...Control block diagrams 337 ...
Страница 338: ...Control block diagrams 338 ...
Страница 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...