Chapter 5: Technical specifications
ZP2 Series Installation Manual
115
Typical expansion board current
consumption
Network board
DACT board
DACT board (with GPRS board)
Loop board [1]
Peripherals boards [1]
2010-2-PIB
2010-2-PIB-8I
2010-2-PIB-8O
2010-2-PIB-8I8O
Zone LED boards
20/24-zones
40-zones
50 mA at 24 VDC
45 mA at 24 VDC
100 mA at 24 VDC
50 mA at 24 VDC
26 mA at 24 VDC
25 mA at 24 VDC
16 mA at 24 VDC
26 mA at 24 VDC
12 mA at 24 VDC
14 mA at 24 VDC
Quiescent current (Imax a) [2]
2.5 A max. at 24 VDC
Alarm current (Imax b) [3]
4 A max. at 24 VDC
[1] No loads connected.
[2] Imax. a is the rated maximum output current which can be supplied continuously.
[3] Imax. b is the rated maximum output current which can be supplied for a short duration in
which battery charging is not required.
Battery and battery charger specifications
For recommended battery specifications, see “Battery maintenance” on page
111.
Type
Sealed lead-acid batteries (2X)
Battery charging voltage
27.3 V at 20ºC – 36 mV/ºC
Battery charging current
1.2 A max.
Low battery indication
23.6 VDC
±
1% at 25ºC
Note:
Additional 0.2 V (max.) drop if Imax b current in battery
cables.
System shutdown warning
21.5 VDC
±
1% at 25ºC
System shutdown (for battery
protection)
21 VDC
±
1% at 25ºC
LCD specifications
Display type
240 x 128 dot graphic LCD (monochromatic)
LCD dimensions (L x W)
83 x 44 mm (active area)
Backlight type
LED style
Backlight colour
White
Summary of Contents for ZP2 Series
Page 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Page 6: ...iv ZP2 Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Page 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Page 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Page 148: ......