Chapter 3: Configuration and commissioning
90
ZP2 Series Installation Manual
The default control panel output groups are shown below.
Note:
This option is not available on repeater panels.
Table 51: Default output groups
Group number
Type
Description
1
SND
Sounder and supervised outputs.
301
PRG
Nonsupervised relay outputs. These outputs are assigned
to this group during autosetup.
801
EXTIN
Extinguishing device outputs. [1]
971
FR
Fire routing outputs. This group is only available on
control panels with the corresponding fire routing controls.
981
FP
Fire protection outputs. This group is only available on
control panels with the corresponding fire protection
controls.
991
ALARM [2]
Outputs activated when the control panel is in alarm
status.
992
FAULT [2]
Outputs activated when the control panel is in fault status.
993
DIS [2]
Outputs activated when the control panel is in disable
status.
994
TEST [2]
Outputs activated when the control panel is in test status.
[1] Extinguishing output groups are only activated with EN 54 type C alarm confirmation.
[2] These output groups are not configurable.
Configurable options for output groups are shown below.
Table 52: Configurable options for output groups
Option
Description
Group_n
Configures the output group number
Type
Configures the output group type
Control
Enables or disables the output group
[BLANK]
Output description
To configure a default output group:
1. Select Field setup from the Main menu, and then select Output groups.
2. Select Output groups.
A list of the available output groups is displayed. Press F3 (Search) to search
by group number. Press F4 (Delete) to delete an output group.
3. Select the output group to configure.
You cannot change the group number or output group type for a default
output group.
Summary of Contents for ZP2 Series
Page 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Page 6: ...iv ZP2 Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Page 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Page 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Page 148: ......