Chapter 1: Introduction
12
ZP2 Series Installation Manual
Indication of remote and local events on the LCD
The local control panel ID is always displayed on the LCD (see Figure 3 on page
10).
If your control panel forms part of a fire network, the event notification includes
the panel ID reporting the event as follows:
•
If the panel ID matches the local ID, then the event relates to the local control
panel
•
If the panel ID does not match the local ID, then the event is reported by the
remote control panel with the panel ID indicated
Repeater panels are installed only in fire networks and by default have a network
board installed. Fire alarm control panels must have a network board installed to
connect to a fire network.
Acoustic indicators
The control panel buzzer acts as an acoustic indicator to highlight system events.
Table 6: Control panel acoustic indicators
Indication
Description
The buzzer sounds continuously
Indicates a fire alarm or a system fault
The buzzer sounds intermittently (long tone) [1] Indicates all other faults
The buzzer sounds intermittently (short tone) [1] Indicates a condition
[1] A long tone is 50% ON and 50% OFF. A short tone is 25% ON and 75% OFF.
Conditions
A summary of system events logged as conditions is shown below.
Table 7: System events logged as conditions
Condition type
Description
Alert
A device is in alarm but the system is waiting for an
additional alarm event to confirm the zone alarm
Configuration device connected
A control panel configuration session is initiated via an
external device (PC, laptop, etc.)
Date and time not set
The system started but the date and time are not set
Disablements
A control panel feature or device is disabled
Event log full
The control panel event log is full
Extinguishing status [1]
Extinguishing is blocked, disabled, or has a fault
Extinguishing I/O device [1]
An extinguishing I/O device is active, being tested, is
disabled, or has a fault
Input activation
An input is activated (subject to configuration)
Summary of Contents for ZP2 Series
Page 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Page 6: ...iv ZP2 Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Page 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Page 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Page 148: ......