Chapter 3: Configuration and commissioning
ZP2 Series Installation Manual
47
Repeat the above steps to end the zone test.
When an alarm is activated in a zone in test:
•
The zone test is confirmed on the LCD while the alarm is active
•
If a zone board is installed and the corresponding zone is included on the
zone board, then the zone alarm LED is flashing or steady (depending on the
source of the alarm)
•
Fire routing, fire protection, sounders, and programmable activations are not
activated
•
The control panel resets the initiating device after 5 seconds and clears the
alarm (manual call points must first be closed before an automatic reset can
be applied)
•
The event is recorded in the event log
When there is a fire alarm in any zone that is
not
in test, the control panel
responds to the alarm event as configured.
Testing control panel input activation
To test activation of an input:
1. Determine the input functionality (consult your fire system installation details).
2. Select Service mode from the Test menu, and then select Local or Global.
Service mode ensures that outputs are not accidentally activated during input
tests. Set Service mode to Global to avoid local and network output
activation. For more information, see “Activating service mode” on page 49.
3. Activate the input device according to the device instructions.
4. Check that the control panel reports the input activation as expected (this
depends on the input configuration, device type, etc.).
When the test is complete, reset the control panel and exit service mode.
Testing control panel and loop output activation
To test activation of an output:
1. Select Test from the Main menu.
2. Select Output test from the Test menu, and then select Panel outputs or Loop
outputs.
3. Select the output you want to test, and then select YES (to activate the
output) or NO (to deactivate the output).
4. Press the jog dial again to end the test.
5. Press F2 (Exit) to exit the menu.
Summary of Contents for ZP2 Series
Page 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Page 6: ...iv ZP2 Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Page 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Page 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Page 148: ......