Chapter 3: Configuration and commissioning
ZP2 Series Installation Manual
87
Type
Description
FRAK1
Fire routing acknowledgement (type 1). The input receives
acknowledgement from the remote monitoring equipment that the fire
routing signal was received correctly. If the acknowledgement is not
received within 100 seconds of fire routing activation, the control panel
reports a fire routing fault.
FRAK2
Fire routing acknowledgement (type 2). The input receives
acknowledgement from the remote monitoring equipment that the fire
routing signal was received correctly. If the acknowledgement is not
received within 240 seconds of fire routing activation, the control panel
reports a fire routing fault.
FPAK1
Fire protection acknowledgement (type 1). The input receives
acknowledgement from remote fire protection equipment. If the
acknowledgement is not received within 100 seconds of fire protection
activation, the control panel reports a fire protection fault.
FPAK2
Fire protection acknowledgement (type 2). The input receives
acknowledgement from remote fire protection equipment. If the
acknowledgement is not received within 240 seconds of fire protection
activation, the control panel reports a fire protection fault.
FP_FT
Fire protection fault. Used to indicate remote faults in fire protection
equipment.
FBFSD
FBF sounders disable. The input is configured to interface to remote
FBF equipment to disable or enable sounders.
UKSB
British school class change. Activation activates sounders for school
class change indication.
MSP
Manual call point alarm (sprinkler).
MHA
Manual call point alarm (“hausalarm”).
KEYSW
Keyswitch access. Activation enables the Operator access level for the
control panel (no password required). Only one input per control panel
can be configured to use this mode.
To enable or disable a control panel input:
1. Select Field setup from the Main menu.
2. Select Panel I/O configuration.
3. Select Panel inputs, and then select the corresponding input.
4. In the Control option, select ENB (enable), DIS (disable), DIS_D (disable in
day mode), or DIS_N (disable in night mode).
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Summary of Contents for ZP2 Series
Page 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Page 6: ...iv ZP2 Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Page 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Page 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Page 148: ......