Chapter 3: Configuration and commissioning
ZP2 Series Installation Manual
77
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select BMS Config.
3. Configure all required settings.
Initpan is only required when using Modbus in Zonepoint mode.
Zonepoint mode implements Modbus services for 32 networked fire panels
with consecutive addresses (for example, 1 to 32 if the address of the first
panel is defined as 001 in InitPan).
Zone mode implements Modbus services for 128 networked fire panels
(InitPan is not required).
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Field configuration
Use the Field setup menu to access the field configuration options shown below.
Table 39: Field configuration options
Option
Description
Autosetup
Automatically configures installed loop devices to their default
settings.
Loop device configuration
Configures installed loop devices or change default settings.
Zone configuration
Configures zones.
Panel I/O configuration
Configures control panel input and output functionality.
Output groups
Configures output groups.
Activation configuration
Configures output group delays and regional investigation time
options.
Loop class
Configures the installation loop wiring Class (Class A or Class B).
Autosetup
Select Autosetup to automatically configure installed loop devices. Autosetup
assigns a default configuration for each device type detected.
To begin autosetup:
1. Select Field setup from the Main menu, and then select Autosetup.
2. Select the corresponding loop or All loops.
During the search the LCD displays the message “Autosetup in progress”.
When the autosetup is complete the list of detected devices is displayed.
Summary of Contents for ZP2 Series
Page 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Page 6: ...iv ZP2 Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Page 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Page 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Page 148: ......