4. Select the input type.
See Table 48 below for a list of available input types.
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Table 48: Configurable input types
Type
Description
LG (default)
Logged activation. An unlatched condition that generates no indications
but it is only stored on the event log.
T_AL
Technical alarm activation. A latched condition indicated on the LCD
and stored in the event log.
This input type can be used for gas detectors.
T_ALu
Technical alarm activation. An unlatched condition indicated on the LCD
and stored in the event log.
This input type can be used for gas detectors and for connecting to
aspirating detector Alert outputs.
DT_AL
Disable technical alarm inputs. When active, this input disables all the
technical alarm inputs (latched and unlatched).
DET
Detector alarm.
This input type can be used for connecting to aspirating detector Fire1
outputs.
MCP
Manual call point alarm.
This input type can be used for connecting to aspirating detector Fire2
outputs.
PREAL
Prealarm (unlatched).
This input type can be used for connecting to aspirating detector Action
outputs.
RST
Activation resets the panel remotely. To reset again, the input must be
deactivated, and then activated again.
FLT
External fault. Activation generates a latched fault event indicated as an
external fault.
DAY
Day mode. When this input is activated, the control panel switches to
day mode until the next scheduled night mode change (or until the
output is deactivated).
NIGHT
Night mode. When this input is activated, the control panel switches to
night mode until the next scheduled day mode change (or until the
output is deactivated).
FOS
Fault Warning Output Open Supervision. By using a 2010-FS-EOL end-
of-line device, the control panel can supervise the open circuit condition
of the Fault Warning output.
Summary of Contents for ZP2 Series
Page 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Page 6: ...iv ZP2 Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Page 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Page 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Page 148: ......