background image

F300-28-00 

I56-1974-006R 

Fire•Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472, 203-484-7161

Before installing detectors, please thoroughly read the NEMA Guide for Proper Use of Smoke Detectors in Duct Applications, which 
provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are avail-
able from NEMA (National Electrical Manufacturers Association, 2101 L Street NW, Washington, DC 20037). NFPA Standards 72 and 
90A should also be referenced for detailed information. 

NOTICE:

 This manual shall be left with the owner/user of this equipment.

IMPORTANT:

 This detector must be tested and maintained regularly following NFPA 72 requirements. The detector should be cleaned 

at least once a year.

GENERAL DESCRIPTION

An HVAC system supplies conditioned air to virtually every area of a building. Smoke introduced into this air duct system is distributed 
to the entire building. Smoke detectors designed for use in air duct systems are used to sense the presence of smoke in the duct.
The D350RPL air duct smoke detector is a photoelectric detector. This smoke detection method combines with an efficient housing 
design that samples air passing through a duct and allows detection of a developing hazardous condition. When sufficient smoke is 
sensed, an alarm signal is initiated at the fire control panel monitoring the detector, and appropriate action can be taken to shut off 
fans, blowers and change over air handling systems, etc. This can prevent the distribution or it can isolate toxic smoke and fire gases 
throughout the areas served by the duct system.
Two LEDs on each detector may illuminate, if programmed by the system control panel, to provide a local alarm indication. There 
is also a remote alarm output for use with auxiliary devices. The D350RPL has remote test capability with the RTS451/RTS451KEY 
Remote Test Station.
The D350RPL incorporates a cover tamper feature. When the cover is removed for more than 20 minutes, the unit loses communication 
at the panel, a trouble is indicated at the panel and the alarm relay switches states thereby shutting down fans, dampers and blowers. 
In the case when the sensor is removed or when there is no power to the unit, only a trouble is indicated at the panel (alarm relay 
does not work any longer).

CONTENTS OF THE DUCT SMOKE DETECTOR HOUSING KIT

The D350RPL Duct Smoke Detector consists of the following items (See Figure 1.):

Figure 1. Exploded view of duct smoke detector components:

CONDUIT 

HOLES

DETECTOR 

HOUSING

SAMPLING 

TUBE 

FILTERS

TERMINAL 

STRIP

POWER 

BOARD

COVER MOUNTING SCREWS

FOAM GASKETS

SAMPLING 

TUBE

DETECTOR 

BOARD

DETECTOR 

COVER

NOTE:

 For ducts over 1

1

2

 feet, longer sampling tubes must be ordered to complete the installation. They must be the correct length for the 

width of the duct where they will be installed. See Table 1 on page 3 to determine the sampling tube required for different duct widths.

Contents Of The Duct Smoke Detector

1.  Complete  duct  smoke  detector  assembly 

with sensor

2.  Two #10 x 1

1

4

˝ sheet metal mounting screws

3.  Two sampling tube filters
4.  One test magnet
5.  Drilling template
6.  Two foam gaskets
7.  Four  #6-self  tapping  mounting  screws  for 

the  sampling  tube  and  optional  exhaust 
tube extension

8.  One sampling tube end cap
9.  One plastic sampling tube
10. One  #8  self-tapping  screw  for  plastic  sam-

pling tube

NOTE:

 A detector sensor board DOES NOT need 

to be ordered separately.

D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR 

WITH EXTENDED AIR SPEED RANGE 

INSTALLATION AND MAINTENANCE INSTRUCTIONS

H0129-00

I56-1974-006R

Summary of Contents for Fire-Lite Alarms D350RPL

Page 1: ...m control panel to provide a local alarm indication There is also a remote alarm output for use with auxiliary devices The D350RPL has remote test capability with the RTS451 RTS451KEY Remote Test Station The D350RPL incorporates a cover tamper feature When the cover is removed for more than 20 minutes the unit loses communication at the panel a trouble is indicated at the panel and the alarm relay...

Page 2: ...but less than 8 feet 2 4m wide 3 Step 4 2 Installation for ducts more than 8 feet 2 4m wide 4 Step 5 Install the filters 4 Step 6 Field wiring 4 Step 7 Perform detector check 5 Step 8 Install the cover 5 Step 9 Detector Maintenance and Test Procedures 5 1 Verify Duct Air Flow Direction And Velocity The D350RPL duct smoke detector is designed to be used in air handling systems having air velocities...

Page 3: ...rom the detector If the tube is shorter than the width of the air duct install the end cap into the sampling tube as shown in Figure 4 Sampling tubes over 3 ft 0 91m long must be supported at the end opposite the duct smoke detector 2 Slide the tube into the housing bushing that meets the air flow first Position the tube so that the arrow points into the air flow as shown in Figure 4 3 Secure the ...

Page 4: ...4 25 to 32mm hole where the flange will be used 5 Install The Filters To install the sampling tube filters simply push the filters into the sampling and exhaust tube holes as shown in Figure 6 If a metal sampling tube is used install the filters over the tube end 6 Field Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical Code and the local codes ...

Page 5: ...water and no more than 1 2 inches of water Because most commercially available manometers cannot accurately measure very low pressure differentials applications with less than 500 FPM of duct air speed may require one of the following 1 the use of a current sourcing pressure transmitter Dwyer Series 607 per Section 9 1 4 or 2 the use of aerosol smoke per section 9 1 2 9 1 2 Air Flow Test using Aer...

Page 6: ...to verify correct operation of the system Remove the detector board to cause a trouble condition locally and at the system control panel Figure 8 Procedure for verifying air flow F300 28 00 6 I56 1974 006R HIGH LOW 9 VOLT BATTERY 9 VOLT BATTERY 9 VOLT BATTERY TO SAMPLING TUBE TO EXHAUST TUBE DIFFERENTIAL PRESSURE TRANSMITTER MODEL 607 01 15 TO 36 VDC SUPPLY 1000 OHM 5 1 WATT RESISTOR VOLT METER FL...

Page 7: ...be out of service Disable the device or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 9 3 Maintenance of Duct Smoke Detectors 9 3 1 Air Filters 1 Turn off power to the system 2 Remove and inspect sampling tube filters 3 If filters are heavily coated with dirt replace them with new filters p n F36 09 11 If they are not heavily coated use a vac...

Page 8: ...ver there is no guarantee that interfer ence will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation be...

Reviews: