YORK
5587001-YSG-A-520 | Start-Up & Operation Guide
74
Table 26: Menus and Submenus (Continued)
Menu
Submenu
Parameters Displayed / Default
Conditions for Parameters Displayed
Units / Range
Commission
(
Manual
Adjustments >
Cooling
(All of the menu
options default
to 0; allow user
to input offset to
the unit)
EVAP-T (Evaporator Temperature)
delta deg F (-10 to 10)
SLP-1 (Suction Line Pressure 1)
psi (-20 to 20)
LLP-1 (Liquid Line Pressure 1)
psi (-20 to 20)
DLP1 (Discharge Line Pressure 1)
psi (-20 to 20)
SLT-1 (Suction Line Temperature 1)
delta deg F (-10 to 10)
LLT-1 (Liquid Line Temperature 1)
delta deg F (-10 to 10)
DLT1 (Discharge Line Temperature 1)
delta deg F (-10 to 10)
SLP-2 (Suction Line Pressure 2)
psi (-20 to 20)
LLP-2 (Liquid Line Pressure 2)
psi (-20 to 20)
DLP2 (Discharge Line Pressure 2)
psi (-20 to 20)
SLT-2 (Suction Line Temperature 2)
delta deg F (-10 to 10)
LLT-2 (Liquid Line Temperature 2)
delta deg F (-10 to 10)
DLT2 (Discharge Line Temperature 2)
delta deg F (-10 to 10)
(
Network
(Refer to
DevName (Displays the Device Name;
Could be Changed by User)
Address (MAC address)
IP Address
TimeZone / Central)
Eastern, Central, Mountain, Pacific, Newfoundland,
Atlantic, Alaska, Hawaii
Descrip (User to Enter Text, if Required)
Comm-S (Displays the Network Status)
Not Configured, Active, Waiting For Poll For
Master, Not Received Token For Long, Duplicate
MAC Address, Forcing BAUD, Remote Trunk
FCBusMode (On units with a BACnet IP
card installed, BACnet MS/TP, Modbus,
and N2 are not functional. Select one of
the available parameters.)
Wired Field Bus, Wireless Field Bus, N2 Field
Bus, Modbus Field Bus, Ethernet Field Bus,
Indeterminate FC Bus Mode
OprBaudRate (Displays the Operating
Baud Rate Used)
Auto, 1200, 9600, 19200, 38400, 76800
BaudRate (Select a Baud Rate) / 38400 Auto, 1200, 9600, 19200, 38400, 76800
IP Mask
IPRouterAddress
StaticIPAddress
StaticIPMask
StaticIPRouterAddress
ApplyStaticIP
DHCP-En
DeviceId
Language / English
English
Units / IP
IP, SI
#NetSensors (Displays the Network
Sensors Connected in SA Bus)
Relearn (Clears the SA Bus Devices in
Memory) / False)
False, True