YORK
Start-Up & Operation Guide | 5587001-YSG-A-520
71
Operation
Menu
Submenu
Parameters Displayed / Default
Conditions for Parameters Displayed
Units / Range
Commission
(
Commissioning Mode / Disable
Disable, Enable
Commissioning Time Remaining
minutes
Extend Commissioning Time / No
No, Yes
SF-C (Supply Fan Command) / OFF
OFF, ON
SF-O (Fan % Command) / 0%
% (0–100)
Supply Fan VFD 2
OFF, ON
Econ (Economizer Damper %
Command) / 0%
% (0–100)
EF-C (Exhaust Fan Command) / OFF
OFF, ON
EF-O (Exhaust Fan VFD % Command)
%
Exhaust Fan VFD 2
OFF, ON
Humidifier Command / OFF
OFF, ON
Humidifier % Command / 0%
% (0–100)
HREAFBD-C (Heat Recovery EA Face
Bypass Damper Command) / Close
Close, Open
Commissioning
Mode >
Air Handler
HRW-C (Heat Recovery Wheel
Command) / OFF
OFF, ON
HRW-O (Heat Recovery Wheel Output)
/ 0%
% (0–100)
EAD-O (Exhaust Damper % Command)
/ 0%
% (0–100)
FaultOut1 / OFF
OFF, ON
FaultOut2 / OFF
OFF, ON
IsoDmpr (Isolation Damper) / Close
Close, Open
VAV Box (MZVAV Box Heat Command)
/ OFF
OFF, ON
Commissioning
Mode > Cooling
Commissioning Mode / Disable
Disable, Enable
Commissioning Time Remaining
minutes
Extend Commissioning Time / No
No, Yes
SF-C (Supply Fan Command)
OFF, ON
SF-O (Fan % Command) / 0%
% (0–100)
C1A (Compressor 1A Command)
OFF, ON
ModCompOut (Modulating Compressor
Output)
% (0–100)
C1B (Compressor 1B Command) / OFF
OFF, ON
C2A (Compressor 2A Command) / OFF
OFF, ON
C2B (Compressor 2B Command) / OFF
OFF, ON
CF-1A (Condenser Fan 1A) / OFF
OFF, ON
ModCondFan1Out (Modulating
Condenser Fan 1 Output)
% (0–100)
CF-1B (Condenser Fan 1B) / OFF
OFF, ON
CF-2A (Condenser Fan 2A) / OFF
OFF, ON
ModCondFan2Out (Modulating
Condenser Fan 2 Output)
% (0–100)
CF-2B (Condenser Fan 2B) / OFF
OFF, ON
HGR (Hot Gas Reheat Command) / 0%
% (0–100)
Table 26: Menus and Submenus (Continued)