YORK
5587001-YSG-A-520 | Start-Up & Operation Guide
104
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
C1A-Starts
AV
29941
R
C1A-Starts
Compressor
Number Times
ON 1A
Displays the compressor 1A start
count
C1B-Starts
AV
29942
R
C1B-Starts
Compressor
Number Times
ON 1B
Displays the compressor 1B start
count
C2A-Starts
AV
29944
R
C2A-Starts
Compressor
Number Times
ON 2A
Displays the compressor 2A start
count
C2B-ASCDTmr
AV
29945
R
C2B-ASCDTmr
Anti-Short Cycle
Delay Time
Remaining 2B
Displays the time remaining for
compressor 2B to turn ON (seconds)
C2BOnTimer
AV
29947
R
C2BOnTimer
Min. ON Time
Remaining 2B
Displays the minimum time remaining
for compressor 2B to turn OFF
(seconds)
C2B-RunTime
AV
29948
R
C2B-RunTime
Compressor
Accumulated
Runtime 2B
Displays the total runtime for
compressor 2B (hours)
C2B-Starts
AV
29950
R
C2B-Starts
Compressor
Number Times
ON 2B
Displays the compressor 2B start
count
ClgCapLim
AV
29964 R/W
ClgCapLim
Cooling Capacity
Limit
A BAS command to adjust the
cooling capacity limit (0–100%)
CoastTime
AV
29966 R/W
CoastTime
Coast Time
A BAS command for unit to operate
in coast mode (0–120 minutes)
DATCapAlmOffset
AV
29967 R/W
DATCapAlmOffset
DAT Capability
Alarm Offset
A BAS command to adjust alarm
for DAT difference from setpoint
(1.0–10.0°F)
EAHR-T
AV
29970
R
EAHR-T
Exhaust Air Heat
Recovery Temp
Displays the exhaust air energy
recovery temperature (°F)
EF-Flow
AV
29971
R
EF-Flow
Exhaust Flow
Value
Displays the return airflow (CFM)
FFILT-DP
AV
29972
R
FFILT-DP
Final Filter
Differential
Pressure
Displays the final filter differential
pressure (iwg)
H1-Starts
AV
29973
R
H1-Starts
Heating Number
Times ON 1
Displays the heating start counts for
stage 1
H2-Starts
AV
29974
R
H2-Starts
Heating Number
Times ON 2
Displays the heating start counts for
stage 2
H3-Starts
AV
29975
R
H3-Starts
Heating Number
Times ON 3
Displays the heating start counts for
stage 3
H4-Runtime
AV
29977
R
H4-Runtime
Heating Stage
4 Accumulated
Runtime
Displays the total runtime for stage 4
heating (hours)
H4-Starts
AV
29979
R
H4-Starts
Heating Number
Times ON 4
Displays the heating start counts for
stage 4
H5-Runtime
AV
29981
R
H5-Runtime
Heating Stage
5 Accumulated
Runtime
Displays the total runtime for stage 5
heating (hours)
Table 32: BACnet Points List (Continued)