YORK
5587001-YSG-A-520 | Start-Up & Operation Guide
110
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
C2A-S
MV
29618
R
C2A-S
Compressor 2A
Status
Displays the status of compressor 2A
0 = OFF/idle
1 = ON/minimum ON time
2 = ON/normal command
3 = OFF/cooling is disabled
C1A-En
MV
29619 R/W
C1A-En
Compressor 1A
Enabled
A BAS command to enable
compressor 1A 0 = YES 1 = NO
C1B-En
MV
29620 R/W
C1B-En
Compressor 1B
Enabled
A BAS command to enable
compressor 1B 0 = YES 1 = NO
C2A-En
MV
29622 R/W
C2A-En
Compressor 2A
Enabled
A BAS command to enable
compressor 2A 0 = YES 1 = NO
COMP1-A
MV
29639
R
COMP1-A
Compressor
Safety Chain 1
Displays the status of CKT 1 safety
chain 0 = normal 1 = alarm
COMP2-A
MV
29640
R
COMP2-A
Compressor
Safety Chain 2
Displays the status of CKT 2 safety
chain 0 = normal 1 = alarm
COMP1-LO
MV
29643
R
COMP1-LO
Compressor
Safety Chain
Lockout 1
Displays the status of CKT 1 safety
chain lockout
0 = normal 1 = lockout
COMP2-LO
MV
29644
R
COMP2-LO
Compressor
Safety Chain
Lockout 2
Displays the status of CKT 2 safety
chain lockout
0 = normal 1 = lockout
LPS1
MV
29647
R
LPS1
Low Pressure
Safety 1
Displays the low pressure system 1
safety alarm 0 = normal 1 = alarm
LPS2
MV
29648
R
LPS2
Low Pressure
Safety 2
Displays the low pressure system 2
safety alarm 0 = normal 1 = alarm
LPS1-LO
MV
29651
R
LPS1-LO
Low Pressure
Lockout 1
Displays the low pressure system 1
safety lockout
0 = normal 1 = lockout
LPS2-LO
MV
29652
R
LPS2-LO
Low Pressure
Lockout 2
Displays the low pressure system 2
safety lockout
0 = normal 1 = lockout
Htg-En
MV
29707 R/W
Htg-En
Heating Mode
Enabled For
Operation
A BAS command that allows the unit
to be placed in a heating mode
0 = OFF 1 = ON
Htg-S
MV
29708
R
Htg-S
Heating Status
Displays the active heating status
0 = OFF/idle
1 = ON
2 = SAT tempering
3 = morning warm-up
FSHW
MV
29712
R
Water FS
Low Temp Water
Coil Freeze Stat
Displays the status of low
temperature water coil freezestat
0 = normal 1 = alarm
HtgUnocc-En
MV
29724 R/W
HtgUnocc-En
Unoccupied
Heating Enabled
A BAS command to enable UNOCC
heating 0 = NO 1 = YES
VAV Box
MV
29727
R
VAV Box
MZ VAV Box Heat
Command
Displays the command of MZVAV
box heat 0 = OFF 1 = ON
H1
MV
29732
R
H1
Heating Stage
Command 1
Displays the command of heating
stage 1 0 = OFF 1 = ON
H2
MV
29733
R
H2
Heating Stage
Command 2
Displays the command of heating
stage 2 0 = OFF 1 = ON
Table 32: BACnet Points List (Continued)