YORK
Start-Up & Operation Guide | 5587001-YSG-A-520
119
Operation
Table 33: Faults List (Continued)
Fault Type
Description
Caused By
ServicePriority
HGRH locked out - valve stuck open
HGRH valve, hot gas flowing to reheat coil
when flow expected to be OFF
ServicePriority
HGRH locked out - valve stuck closed
HGRH valve, hot gas not flowing to reheat
coil when flow expected
ServicePriority
Main controller calibration error
Cycle power to the unit. If error returns,
contact technical support
ServicePriority
Option controller calibration error
Cycle power to the unit. If error returns,
contact technical support
ServicePriority
Condenser 1 controller calibration error
Cycle power to the unit. If error returns,
contact technical support
ServicePriority
Condenser 2 controller calibration error
Cycle power to the unit. If error returns,
contact technical support
ServicePriority
Building system interface board controller
calibration error
Cycle power to the unit. If error returns,
contact technical support
ServicePriority
DAT sensor failure
Sensor input out of expected range. Open
or shorted circuit
ServicePriority
OAT sensor failure
Sensor input out of expected range. Open
or shorted circuit
ServicePriority
RAT sensor failure
Sensor input out of expected range. Open
or shorted circuit
ServicePriority
Building pressure sensor failure
Sensor input out of expected range. Open
or shorted circuit
ServicePriority
Return fan pressure sensor failure
Sensor input out of expected range. Open
or shorted circuit
ServicePriority
Evaporator coil temperature 1 sensor failure
Sensor input out of expected range. Open
or shorted circuit
ServicePriority
C1A shutdown - exceeded operating envelope
limits
Variable speed drive compressor
envelope control: This output shows
disabled when a shutdown occurred due
to the variable speed drive compressor
exceeding its operating envelope limits.
The rule is that the compressor is to
remain off for 10 minutes.
Service
Circuit 1 shutdown due to safety chain
One of the safety chain switches in circuit
1 has opened
Service
Circuit 2 shutdown due to safety chain
One of the safety chain switches in circuit
2 has opened
Service
MAT sensor failure
Sensor input out of expected range. Open
or shorted circuit
Service
Outside air humidity sensor failure
Sensor input out of expected range. Open
or shorted circuit
Service
Pre-filter pressure sensor failure
Sensor input out of expected range. Open
or shorted circuit
Service
Final filter pressure sensor failure
Sensor input out of expected range. Open
or shorted circuit
Service
Return air humidity sensor failure
Sensor input out of expected range. Open
or shorted circuit
Service
Heat entering temperature sensor failure
Sensor input out of expected range. Open
or shorted circuit