YORK
5587001-YSG-A-520 | Start-Up & Operation Guide
106
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
RAD-POS
AV
30026
R
RAD-POS
Return Air
Damper Position
Displays the status of return air
damper position (%)
RunContAlmDly
AV
30028 R/W
RunContAlmDly
Unit Running
Continuously
Alarm Delay
A BAS command that adjusts unit
running continuously alarm delay
(1–99 hours)
SF-DAT-
SpHighThresh
AV
30029 R/W
SF-DAT-
SpHighThresh
Supply Fan DAT
Setpoint High
Threshold
A BAS command to adjust DAT
based on high supply fan speed
(0–100%)
SF-DAT-
SpLowThresh
AV
30030 R/W
SF-DAT-
SpLowThresh
Supply Fan DAT
Setpoint Low
Threshold
A BAS command to adjust DAT
based on low supply fan speed
(0–100%)
SZVAVClgMinFan
AV
30034 R/W
SZVAVClgMinFan
SZVAV Cooling
Minimum Fan
Speed
A BAS command to adjust SZVAV
cooling minimum fan speed (20–67%)
SZVAVHtgMinFan
AV
30035 R/W
SZVAVHtgMinFan
SZVAV Heating
Minimum Fan
Speed
A BAS command to adjust SZVAV
heating minimum fan speed (20–67%)
UVLight-Rt
AV
30038
R
UVLight-Rt
UV Light Runtime Displays the UV light runtime (hours)
DLP1
AV
30040
R
DLP1
Discharge Line
Pressure 1
Displays the active system 1
discharge line pressure (psi)
DLT1
AV
30041
R
DLT1
Discharge Line
Temperature 1
Displays the active system 1
discharge line temperature (°F)
DLP2
AV
30042
R
DLP2
Discharge Line
Pressure 2
Displays the active system 2
discharge line pressure (psi)
DLT2
AV
30043
R
DLT2
Discharge Line
Temperature 2
Displays the active system 2
discharge line temperature (°F)
DischSuperheat1
AV
30044
R
DischSuperheat1
Discharge
Superheat 1
Displays the active system 1
discharge superheat temperature (°F)
DischSuperheat2
AV
30045
R
DischSuperheat2
Discharge
Superheat 2
Displays the active system 2
discharge superheat temperature (°F)
SucSuperheat1
AV
30046
R
SucSuperheat1
Suction
Superheat 1
Displays the active system 1 suction
superheat temperature (°F)
SucSuperheat2
AV
30047
R
SucSuperheat2
Suction
Superheat 2
Displays the active system 2 suction
superheat temperature (°F)
LLSubcool1
AV
30048
R
LLSubcool1
Liquid Line Sub-
Cooling 1
Displays the active system 1 liquid
line sub-cooling temperature (°F)
LLSubcool2
AV
30049
R
LLSubcool2
Liquid Line Sub-
Cooling 2
Displays the active system 2 liquid
line sub-cooling temperature (°F)
SatDischTemp1
AV
30050
R
SatDischTemp1
Saturated DAT 1 Displays the active system 1
saturated DAT (°F)
SatDischTemp2
AV
30051
R
SatDischTemp2
Saturated DAT 2 Displays the active system 2
saturated DAT (°F)
SatLLTemp1
AV
30052
R
SatLLTemp1
Saturated Liquid
Line Temperature 1
Displays the active system 1
saturated liquid line temperature (°F)
SatLLTemp2
AV
30053
R
SatLLTemp2
Saturated Liquid
Line Temperature 2
Displays the active system 2
saturated liquid line temperature (°F)
SatSucTemp1
AV
30054
R
SatSucTemp1
Saturated Suction
Temperature 1
Displays the active system 1 saturated
suction line temperature (°F)
Table 32: BACnet Points List (Continued)