YORK
Start-Up & Operation Guide | 5587001-YSG-A-520
99
Operation
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
OprSSO
AV
29537
R
OprSSO
Operational Zone
Temperature
Setpoint Offset
Displays the operational zone
temperature setpoint offset (Δ°F)
NetSSO
AV
29540 R/W
NetSSO
Network Override
Space Setpoint
Offset
A BAS command to override space
setpoint offset (-5.0 to 5.0 Δ°F)
OprOAT
AV
29541
R
OprOAT
Operational OAT Displays the active OAT (°F)
NetOAT
AV
29543 R/W
NetOAT
Network Override
OAT
A BAS command to override OAT
(-50.0 to 125.0°F)
OprOAH
AV
29544
R
OprOAH
Operational
Outdoor Air
Humidity
Displays the active outside air
humidity (%RH)
OA-Enth
AV
29545
R
OA-Enth
Outdoor Air
Enthalpy
Displays the active outside air
enthalpy (BTU/lb)
NetOAH
AV
29546 R/W
NetOAH
Network Override
Outdoor Air
Humidity
A BAS command to override outside
air humidity (0–100 %RH)
OprOAQ
AV
29547
R
OprOAQ
Operational
Outdoor Air
Quality
Displays the active outdoor air CO
2
(PPM)
NetOAQ
AV
29549 R/W
NetOAQ
Network Override
Outdoor Air
Quality
A BAS command to override outdoor
air CO
2
(PPM)
FanVFD
AV
29551
R
SF-O
Fan % Command Displays the output from the control
to the supply fan VFD (%)
Fan-RT
AV
29554
R
SF-Runtime
Supply Fan
Accumulated
Runtime
Displays the supply fan runtime
(hours)
FanOffDlyCool
AV
29559 R/W
FanOffDlyCool
Fan Off Delay for
Cool
A BAS command to adjust the supply
fan runtime after cooling is turned
OFF (0–255 seconds)
FanOffDlyHeat
AV
29561 R/W
FanOffDlyHeat
Fan Off Delay for
Heat
A BAS command to adjust the supply
fan runtime after heating is turned
OFF (0–30 seconds)
DAT
AV
29564
R
DAT
DAT
Displays the active DAT (°F)
DctPrs
AV
29565
R
DA-P
Discharge Air
Static Pressure
Displays the active discharge air
static pressure (iwg)
DctPrs-Sp
AV
29566 R/W
DctPrs-Sp
Duct Pressure
Setpoint
A BAS command to adjust active
duct static pressure setpoint (iwg)
DctShutdownSp
AV
29567 R/W
DctShutdownSp
Duct Pressure
Shutdown
Setpoint
A BAS command to adjust the
duct static pressure unit shutdown
setpoint (iwg.)
#ClgStgs
AV
29576
R
#ClgStgs
Number of
Cooling Stages
Installed
Displays the number of cooling
stages installed.
MinRtCoolStg
AV
29578
R
MinRtCoolStg
Minimum Runtime
for a Cooling
Stage
Displays the minimum runtime for a
cooling stage (3–10 minutes)
Table 32: BACnet Points List (Continued)